Download IconPrint Icon

BayEnergy® Low voltage cables

GKN

5-cores TN-S acc. to CENELEC HD 603 S1 part 7E


AT514_GKN_4x_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei40-Geschirmt46-Robust

 


Standards

Cable according to CENELEC HD 603 S1 part 7E
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Cu conductor, bare acc. to IEC 60228, round, stranded  
Conductor insulation, elastomer cross-linked acc. to the requirements of HD 603.1  
Core marking acc. to HD 603 S1 part 7E
L1 brown
L2 black
L3 grey
N  blue
 
Inner covering (extruded bedding) with separating strip against bonding  
Outer conductor Cu wires, ceander design, with Cu counter helix  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 yellow longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
3.5

Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit

 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

The design is specially used in 5-conductor TN-S systems with separate neutral (N) and protective earth (PE). This enables an EMC-optimised supply network for reduced electromagnetic interference.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer cross-linked
K concentric outer conductor/screen made of copper
N halogen-free sheath made of PE
RE round conductor, solid
RM round conductor, stranded

Special Designs

Design according to national, international and customer standards

Order Example

GKN 4x50 RM/50 0,6/1kV (3LNPE)


Print Icon

BayEnergy® Low voltage cables

GKN

5-cores TN-S acc. to CENELEC HD 603 S1 part 7E

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GKN      4x 6 RE*/ 6   0,6/1kV  (3LNPE) 4488960 17 535 0.86 96 90 180
GKN      4x10 RE*/10   0,6/1kV  (3LNPE) 4488970 19 755 1.43 160 100 200
GKN      4x16 RM*/16   0,6/1kV  (3LNPE) 4488980 23 1135 2.29 256 120 240
GKN      4x16 RM*/25   0,6/1kV  (3LNPE) 4488990 23 1235 2.29 256 120 240
GKN      4x25 RM*/25   0,6/1kV  (3LNPE) 4488790 27 1665 3.58 400 140 270
GKN      4x35 RM*/35   0,6/1kV  (3LNPE) 4488010 30 2185 5.01 560 160 310
GKN      4x50 RM*/50   0,6/1kV  (3LNPE) 4488850 33 2925 7.15 800 170 340
GKN      4x70 RM*/70   0,6/1kV  (3LNPE) 4488680 39 4095 10.01 1120 200 400
GKN      4x95 RM*/95   0,6/1kV  (3LNPE) 4488870 43 5598 13.59 1520 220 440
GKN     4x120 RM*/120  0,6/1kV  (3LNPE) 4488690 47 7160 17.16 1920 250 490
GKN     4x150 RM*/150  0,6/1kV  (3LNPE) 4488950 53 8490 21.45 2400 270 540
GKN     4x185 RM*/185  0,6/1kV  (3LNPE) 4488955 61 10210 26.46 2960 310 620
GKN     4x240 SM*/240  0,6/1kV (3LNPE) mit C-Leiter n. VDE 4488020 66 13250 34.32 3840 340 670
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.