Download IconPrint Icon

BayEnergy® Low voltage cables

GKN-Flex

3-cores acc. to CENELEC HD 603 S1 part 7E


AT563_GKN-Flex_3x_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei46-Robust42-Flexibel

 


Standards

Cable according to CENELEC HD 603 S1 part 7E
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Cu conductor, bare acc. to IEC 60228
round, finely stranded, conductor category 5
 
Conductor insulation, elastomer cross-linked acc. to the requirements of HD 603.1  
Core marking acc. to HD 603 S1 part 7E
3LPEN: L1 black, L2 red, L3 white.
For 2LNPE: L1 black, L2 brown, N blue
 
Inner covering (extruded bedding) with separating strip against bonding  
Outer conductor Cu wires, ceander design, with Cu counter helix  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 yellow longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
 
3.5
Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit
 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer cross-linked
K concentric outer conductor/screen made of copper
N halogen-free sheath made of PE
RF round conductor, finely stranded

Special Designs

Design according to national, international and customer standards

Order Example

GKN-Flex 3x50 RF/50 0,6/1kV (3LPEN)


Print Icon

BayEnergy® Low voltage cables

GKN-Flex

3-cores acc. to CENELEC HD 603 S1 part 7E

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GKN-FLEX  3x2,5RF*/2,5 0,6/1kV  (2LNPE) mit C-Leiter n. VDE 4488672 14 268 0.36 15 60 120
GKN-FLEX   3x6 RF*/6   0,6/1kV  (3LPEN) 4488674 17 470 0.86 36 70 140
GKN-FLEX   3x6 RF*/6   0,6/1kV  (2LNPE) 4488676 17 470 0.86 36 70 140
GKN-FLEX  3x10 RF*/10  0,6/1kV  (3LPEN) 4488664 19 645 1.43 60 80 160
GKN-FLEX  3x10 RF*10  0,6/1kV   (2LNPE) 4488666 19 645 1.43 120 80 160
GKN-FLEX  3x16 RF*/16  0,6/1kV  (3LPEN) 4488614 22 922 2.29 96 100 190
GKN-FLEX  3x16 RF*/16  0,6/1kV  (2LNPE) 4488616 22 922 2.29 96 100 190
GKN-FLEX  3x25 RF*/25  0,6/1kV  (3LPEN) 4488624 25 1345 3.58 150 110 210
GKN-FLEX  3x50 RF*/50  0,6/1kV  (3LPEN) 4488634 32 2465 7.15 300 140 270
GKN-FLEX  3x70 RF*/70  0,6/1kV  (3LPEN) 4488100 38 3465 10.01 420 160 310
GKN-FLEX  3x95 RF*/95  0,6/1kV  (3LPEN) 4488644 41 4524 13.59 570 170 340
GKN-FLEX 3x150 RF*/150 0,6/1kV  (3LPEN) 4488654 51 6995 21.45 900 210 420
GKN-FLEX 3x185 RF*/185 0,6/1kV  (3LPEN) 4488640 58 7886 26.46 1110 240 480
GKN-FLEX 3x240 RF*/240 0,6/1kV  (3LPEN) mit C-Leiter n. VDE 4488650 65 10210 34.32 1440 270 530
GKN-FLEX 3x300 RF*/300 0,6/1kV  (3LPEN) mit C-Leiter n. VDE 4488652 72 12860 42.90 1800 300 600
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.