Download IconPrint Icon

BayEnergy® Low voltage cables

GKN-Flex

5-cores TN-S acc. to CENELEC HD 603 S1 part 7E


AT564_GKN-Flex_4x_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei40-Geschirmt46-Robust42-Flexibel

 


Standards

Cable according to CENELEC HD 603 S1 part 7E
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Cu conductor, bare acc. to IEC 60228, round, stranded  
Conductor insulation, elastomer cross-linked acc. to the requirements of HD 603.1  
Core marking acc. to HD 308
L1 brown
L2 black
L3 grey
N  blue
 
Inner covering (extruded bedding) with separating strip against bonding  
Outer conductor = protective earth (PE)
Cu wires, ceander design, with Cu counter helix
 
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 yellow longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc.to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
 
3.5
Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit
 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

The design is specially used in 5-conductor TN-S systems with separate neutral (N) and protective earth (PE). This enables an EMC-optimised supply network for reduced electromagnetic interference.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer cross-linked
K concentric outer conductor/screen made of copper
N halogen-free sheath made of PE
RF round conductor, finely stranded, conductor category 5

Special Designs

Design according to national, international and customer standards

Order Example

GKN-Flex 4x50 RF/50 0,6/1kV (3LNPE)


Print Icon

BayEnergy® Low voltage cables

GKN-Flex

5-cores TN-S acc. to CENELEC HD 603 S1 part 7E

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GKN-FLEX 4x2,5RF*/2,5  0,6/1kV  (3LNPE) mit C-Leiter n. VDE 4488580 15 303 0.36 20 70 130
GKN-FLEX  4x6  RF*/6   0,6/1kV  (3LNPE) 4488610 18 553 0.86 48 80 150
GKN-FLEX  4x10 RF*/10  0,6/1kV  (3LNPE) 4488570 20 770 1.43 80 90 170
GKN-FLEX  4x16 RF*/16  0,6/1kV  (3LNPE) 4488810 24 1116 2.29 128 100 200
GKN-FLEX  4x25 RF*/25  0,6/1kV  (3LNPE) 4488820 27 1625 3.58 200 120 230
GKN-FLEX  4x35 RF*/35  0,6/1kV  (3LNPE) 4488830 30 2176 5.01 280 130 260
GKN-FLEX  4x50 RF*/50  0,6/1kV  (3LNPE) 4488840 35 2950 7.15 400 150 290
GKN-FLEX  4x95 RF*/95  0,6/1kV  (3LNPE) 4488860 45 5365 13.59 760 190 370
GKN-FLEX 4x120 RF*/120 0,6/1kV  (3LNPE) 4488670 50 6895 17.16 960 210 410
GKN-FLEX 4x150 RF*/150 0,6/1kV  (3LNPE) 4488880 57 8529 21.45 1200 230 460
GKN-FLEX 4x185 RF*/185 0,6/1kV  (3LNPE) mit C-Leiter n. VDE 4488875 63 9685 26.46 1480 260 520
GKN-FLEX 4x240 RF*/240 0,6/1kV  (3LNPE) mit C-Leiter n. VDE 4488600 71 13795 34.32 1920 290 580
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.