Print Icon

BayEnergy® Low voltage cables

GN-CLN Al

4-cores/5-cores acc. to, resp. based on CENELEC HD 603 S1 part 8B


AT584_GN_CLN_Al_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei46-Robust

 


Standards

Cable acc. to CENELEC HD 603 S1 part 8B (Alse, Alrm),
and/or based on CENELEC HD 603 S1 part 8B (Alsm)
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Al conductor, bare, sector-shaped, solid  
Conductor insulation, elastomer based on HEPR acc. to the requirements of HD 603.1 table 2C  
Core marking acc. to HD 603 S1 part 8B
L1 black
L2 red
L3 white
PE green-yellow
 
Halogen-free sheath made of MDPE (DMP5)  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 blue longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
3.5

Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit

 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation,elastomer based on HEPR
N halogen-free sheath made of PE
CLN armouring made of steel tape with protective outer sheath made of PE
Alse Al conductor, sector-shaped, solid
Alsm Al conductor, sector-shaped, stranded
Alrm Al conductor, round, stranded

Special Designs

Design according to national, international and customer standards

Order Example

GN-CLN 4x150 Alse 0,6/1kV (3LPEN)


Print Icon

BayEnergy® Low voltage cables

GN-CLN Al

4-cores/5-cores acc. to, resp. based on CENELEC HD 603 S1 part 8B

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GN-CLN     4x25  Alrm 0,6/1 kV  (LLNPE) 4212764 26 970 2.35 200 140 270
GN-CLN     4x50  Alrm 0,6/1 kV  (LLNPE) 4212774 33 1480 4.70 400 170 340
GN-CLN     4x70  Alrm 0,6/1 kV  (LLNPE) 4212784 37 1940 6.58 560 190 380
GN-CLN     4x150 Alse 0,6/1 kV  (3LPEN) 4212504 45 2490 14.10 1200 230 460
GN-CLN     4x150 Alsm 0,6/1 kV  (3LPEN) 4213504 48 2600 14.10 1200 250 490
GN-CLN     4x240 Alse 0,6/1 kV  (3LPEN) 4212704 56 3870 22.56 1920 290 570
GN-CLN     5x35  Alrm 0,6/1 kV  (3LNPE) 4212724 32 1370 3.29 350 170 330
GN-CLN     5x95  Alrm 0,6/1 kV  (3LNPE) 4212734 46 2880 8.93 950 240 470
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.