Download IconPrint Icon

BayEnergy® Low voltage cables

GN-CLN

3-cores/4-cores/5-cores acc. to HD 603 S1 part 8B


AT594_GN_CLN_en
RoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei46-Robust

 


Standards

Cable according to CENELEC HD 603 S1 part 8B
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Cu conductor, bare acc. to IEC 60228
round, solid for cables with conductor ≤ 10 mm² and
round, stranded for cables with conductors ≥ 16 mm²
 
Conductor insulation, elastomer cross-linked acc. to the requirements of HD 603.1  
Core marking acc. to HD 603 S1 part 8B
L1 black
L2 red
L3 white
N blue
PE green-yellow
 
Inner covering (extruded bedding) with separating strip against bonding  
Armouring made of steel tape  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 blue longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
3.5

Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit

 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer cross-linked
N halogen-free sheath made of PE
CLN armouring made of steel tape with protective outer sheath made of PE

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

GN-CLN 4x50 RM 0,6/1 kV  (LLNPE)


Print Icon

BayEnergy® Low voltage cables

GN-CLN

3-cores/4-cores/5-cores acc. to HD 603 S1 part 8B

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GN-CLN     3x2,5 RE   0,6/1 kV  (3L) 4212572 14 300 0.36 30 80 150
GN-CLN     3x4   RE   0,6/1 kV  (3L) 4212824 15 360 0.57 48 80 160
GN-CLN     4x10  RE   0,6/1 kV  (3LPEN) 4212674 19 715 1.43 160 100 200
GN-CLN     4x16  RM   0,6/1 kV  (3LPEN) 4212664 23 1090 2.29 256 120 240
GN-CLN     4x25  RM   0,6/1 kV  (3LPEN) 4212614 26 1535 3.58 400 140 270
GN-CLN     4x35  RM   0,6/1 kV  (3LPEN) 4212624 29 1960 5.01 560 150 300
GN-CLN     4x50  RM   0,6/1 kV  (3LPEN) 4212634 32 2530 7.15 800 170 330
GN-CLN     4x50  SM   0,6/1 kV  (3LPEN) 4212694 32 2380 7.15 800 170 330
GN-CLN     4x95  RM   0,6/1 kV  (LLNPE) 4212644 42 4700 13.59 1520 220 430
GN-CLN     4x150 RM   0,6/1 kV  (3LPEN) 4212654 52 7230 21.45 2400 270 530
GN-CLN     5x4   RE   0,6/1 kV  (3LNPE) 4212834 17 485 0.57 80 90 180
GN-CLN     5x10  RE   0,6/1 kV  (3LNPE) 4212814 20 850 1.43 200 110 210
GN-CLN     5x10  RM   0,6/1 kV  (3LNPE) 4212680 22 910 1.43 200 110 220
GN-CLN     5x16  RM   0,6/1 kV  (3LNPE) 4212794 25 1300 2.29 320 130 250
GN-CLN     5x25  RM   0,6/1 kV  (3LNPE) 4212684 29 1825 3.58 500 150 290
GN-CLN     5x35  RM   0,6/1 kV  (3LNPE) 4212744 31 2360 5.01 700 160 320
GN-CLN     5x50  RM   0,6/1 kV  (3LNPE) 4212714 35 3105 7.15 1000 180 360
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.