3-cores based on CENELEC HD 603 S1 part 7E


AT523_GKN_Alsm_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei46-Robust

 


Standards

Cable based on CENELEC HD 603 S1 part 7E
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Al conductor, bare, sector-shaped, stranded  
Conductor insulation, elastomer based on HEPR acc. to the requirements of HD 603.1 table 2C  
Core marking acc. to HD 603 S1 part 7E
L1 black
L2 red
L3 white
 
Inner covering (extruded bedding) with separating strip against bonding  
Outer conductor = protective earth (PE)
Cu wires, ceander design, with Cu counter helix
 
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 yellow longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
3.5
Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit
 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer besed on HEPR
K concentric outer conductor/screen made of copper
N halogen-free sheath made of PE
Alsm Al conductor, sector-shaped, stranded

Special Designs

Design according to national, international and customer standards

Order Example

GKN 3x240 Alsm/150 Cu 0,6/1kV (3LPEN)


Print Icon

BayEnergy® Low voltage cables

GKN Alsm

3-cores based on CENELEC HD 603 S1 part 7E

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GKN   3x35 Alsm*/25 Cu 0,6/1kV  (3LPEN) 4488250 25 930 3.29 210 130 260
GKN   3x50 Alsm*/16 Cu 0,6/1kV  (3LPEN) 4488160 28 1045 4.70 300 150 290
GKN   3x50 Alsm*/35 Cu 0,6/1kV  (3LPEN) 4488920 29 1220 4.70 300 150 290
GKN   3x70 Alsm*/35 Cu 0,6/1kV  (3LPEN) 4488910 32 1510 6.58 420 170 330
GKN   3x95 Alsm*/50 Cu 0,6/1kV  (3LPEN) 4488400 35 1860 8.93 570 180 360
GKN  3x150 Alsm*/95 Cu 0,6/1kV  (3LPEN) 4488070 44 3028 14.10 900 230 450
GKN 3x240 Alsm*/150 Cu 0,6/1kV  (3LPEN) 4488275 53 4635 22.56 1440 270 540
GKN 3x300 Alsm*/185 Cu 0,6/1kV  (3LPEN) mit C-Leiter n. VDE 4488890 61 6285 28.20 1800 380 750
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.