Power EMV PUR 1x...
0,6/1 kV

BayMotion® Flexible power connection cables screened acc. to Bayka company standard


IT123_EMV-Flex 1x...Power_en
RoHS_LogoREACH_LogoCE_Logo

 

08-Trogverlegung04-Rohrverlegung16-Inhouse28-Ölbeständig23-Halogenfrei40-Geschirmt46-Robust42-Flexibel54-Verlegung -25

 


Standards

Similar to HD 603 S1,
oil resistance according to DIN EN 60811-404,
free from halogen according to IEC 60754-1,
corrosivity of the fire gases according to IEC 60754-2.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Conductor resistance
acc. to EN 60228 (DIN VDE 0295)
Conductor class 5
 
Rated voltage U0/U kV 0.6/1
Testing voltage kV 4
Current carrying capacity
BayMotion®-Flex  
Conductor resistance Ω/km
(at 20 °C)
Laying
in pipe *)
A  
Laying
in air*)
A  
 1x50  0.386  209  207
 1x70  0.272  256  263
 1x95  0.206  307  325
 1x120  0.161  349  380
 1x150  0.129  393  437
 1x185  0.106  445  507
 1x240  0.0801  517  604
 1x300  0.0641  583  697
 1x400 0.0486 663 811

*) Consider the current carrying capacity requirements of VDE 0276-603 part 5G
 

Permissible temperature range °C
during operation
during installation/laying
highest permissible operating temperature (conductor)

-40 to +70
-25 to +70
+90
 
   

Design
Copper stranded wire
Conductor insulation
Colour of cores
Double screening

Outer sheath

 

Bare, finely-stranded according to EN 60228, conductor class 5
Special PE-based elastomer
Black, green-yellow
Laminated aluminium foil + braid made from tin-coated copper wires, nominal value of optical covering 80 %
Crosslinked special elastomer

Application

BayMotion® EMC-Flex power connection cable as a robust and flexible power, connection and link cable for use in plant and mechanical engineering.

The cable has very good oil resistance and guarantees a long service life in a contaminated environment, e.g. with connections of transformers.

The optimised screening enables fault-free operation in EMC-sensitive environments (electromagnetic compatibility).­

The cable is suitable for permanent laying in dry, moist and wet rooms, for outdoor-use and for laying in the ground, if an additional protection, e. g. pipe conduit or trough channel is used. Furthermore, the cable is particularly suitable for flexible use without additional mechanical load.

Type Designation Codes

RF round conductor, finely stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

BayMotion®-EMV-Flex 1x240  0,6/1 kV


Print Icon

BayMotion® Power connection cables, screened

Power EMV PUR 1x...
0,6/1 kV

BayMotion® Flexible power connection cables screened acc. to Bayka company standard

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
There are no items in your cart.
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.