Print Icon

BayEnergy® Low voltage cables

GKN Alsm

Combi EMC 5-cores TN-S based on CENELEC HD 603 S1 part 7E


AT525_GKN_Alsm_Kombi_Cu_4x_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei40-Geschirmt46-Robust

 


Standards

Cable based on CENELEC HD 603 S1 part 7E
halogen-free acc. to IEC 60 754-1
no corrosive gases acc. to DIN EN 50 267-2-3
no toxic gases acc. to DIN EN 50 305

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Al conductor, bare, sector-shaped, stranded
Cu conductor, bare, sector-shaped, stranded
 
Conductor insulation, elastomer based on HEPR acc. to the requirements of HD 603.1 table 2C  
Core marking
Al conductor black, grey, brown
Cu conductor blue
 
Inner covering (extruded bedding) with separating strip against bonding  
Outer conductor = protective earth (PE)
Cu wires, ceander design, with Cu counter helix
 
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 yellow longitudinal strips, BAYKA, year / month of manufacture, 0.6/1 kV, metre marking
 
Rated voltage U0/U kV 0.6/1
Conductor resistance (direct current at 20 °C) acc. to IEC 60228
Testing voltage (AC voltage, 5 min) kV
acc. to HD 603.1
3.5
Temperature ranges °C
continuous operation
emergency operation (less than 8 h/d, less than 100 h/a)
short-circuit
 
≤ 90
≤ 130
≤ 250

Application

Suitable for installation in the ground, in protective conduits, cable ducts, in open air, for power stations, industry and distribution boards or low-voltage distribution systems.

The design is specially used in 5-conductor TN-S systems with separate neutral (N) and protective earth (PE). This enables an EMC-optimised supply network for reduced electromagnetic interference.

Due to the cross-linked conductor insulation, particularly suitable for higher temperatures in the case of a short-circuit or overload. The PE sheath of the BayEnergy® LV mains cables is particularly robust and distinguishes itself with excellent mechanical properties and increased thermal compressive strength.

Type Designation Codes

G conductor insulation, elastomer based on HEPR
K concentric outer conductor/screen made of copper
N halogen-free sheath made of PE
Alsm Al conductor, sector-shaped, stranded
SM Cu conductor, sector-shaped, stranded

Special Designs

Design according to national, international and customer standards

Order Example

GKN 3x150 Alsm+1x150 SM/ 150 Cu KOMBI 0,6/1 kV (3LNPE)


Print Icon

BayEnergy® Low voltage cables

GKN Alsm

Combi EMC 5-cores TN-S based on CENELEC HD 603 S1 part 7E

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
GKN  3x50 Alsm*+1x50 SM*/50 Cu  KOMBI  0,6/1 kV (3LNPE) 4488935 29 1468 4.70 400 150 300
GKN  3x70 Alsm*+1x70 SM*/70 Cu  KOMBI  0,6/1 kV (3LNPE) 4488805 36 2620 6.58 560 190 370
GKN  3x95 Alsm*+1x95 SM*/95 Cu  KOMBI  0,6/1 kV (3LNPE) 4488265 42 3425 8.93 760 220 430
GKN 3x150 Alsm*+1x150SM*/150Cu  KOMBI  0,6/1 kV (3LNPE) 4488270 51 5234 14.10 1200 260 520
GKN 3x240 Alsm*+1x240SM*/240Cu KOMBI C-Leiter 0,6/1kV (3LNPE) 4488040 65 8572 22.56 1920 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs with different armouring, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.