Print Icon

BayEnergy® Medium voltage cables, XLPE insulation, Cu screen, PE sheath, 1-core

XKDT

1 core, copper based on DIN VDE 0276-620


BT132_en
RoHS_LogoREACH_Logoelectrosuisse_hoch

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig36-Längswasserdicht53-Verlegung -20

 


Standards

Based on DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Cu conductor, round, stranded, compressed  
Extruded inner conductive layer  
Insulation made of cross-linked PE  
Extruded outer conductive layer  
Screen made of Cu wires, with Cu counter helix  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 red longitudinal strips, manufacturer, cable designation, year of manufacture, metre marking
 
Rated voltage kV 12/20
Testing voltage kV 30
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7+8
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

X insulation made of cross-linked polyethylene (XLPE)
K screen made of copper
D longitudinally watertight in the screen section
T outer sheath made of polyethylene (PE)

Cu

copper
rm round, stranded

Special Designs

Design according to customer specifications
Design with improved properties on request

Order Example

XKDT  1x150 Curm/35    20/12kV


Print Icon

BayEnergy® Medium voltage cables, XLPE insulation, Cu screen, PE sheath, 1-core

XKDT

1 core, copper based on DIN VDE 0276-620

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
XKDT  1x50  Curm/16    20/12kV 4726007 32 1107 7.15 250 250 500
XKDT  1x95  Curm/25    20/12kV 4726008 35 1755 13.59 475 275 550
XKDT  1x95  Curm/16    20/12kV 4726009 35 1680 13.59 475 275 550
XKDT  1x150 Curm/35    20/12kV 4726011 38 2354 21.50 750 300 600
XKDT  1x150 Curm/25    20/12kV 4726014 38 2260 21.50 750 300 600
XKDT  1x240 Curm/35    20/12kV 4726016 42 3294 34.32 1200 325 650
XKDT  1x240 Curm/25    20/12kV 4726017 42 3220 34.32 1200 325 650
XKDT  1x300 Curm/35    20/12kV 4726018 44 4144 42.90 1500 350 700
XKDT  1x400 Curm/35    20/12kV 4726019 47 4814 57.20 2000 375 750
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.