BayEnergy® Medium voltage cables, XLPE insulation, Cu screen, PE sheath, 3-cores (stranded)
XKDT-YT
3-cores, copper, overall sheath based on DIN VDE 0276-620









Standards
Based on DIN VDE 0276-620.
The cables are in compliance with RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).
Technical Data
Cu conductor, round, strand, compressed | |
Extruded inner conductive layer | |
Insulation made of cross-linked PE | |
Extruded outer conductive layer | |
Screen made of Cu wires, with Cu counter helix | |
Outer sheath made of halogen-free, robust PE | |
Wear-resistant cable marking 2 red longitudinal strips, manufacturer, cable designation, year of manufacture, metre marking |
|
3 single-core cables, stranded | |
Common protective sheath | |
Rated voltage kV | 12/20 |
Testing voltage kV | 30 |
Cable temperature ºC during laying (min) after laying (max) |
-20 +90 |
Max permissible operating temperature (conductor) °C |
+90 |
Short-circuit temperature °C | +250 |
Current carrying capacity acc. to HD 620 S2:2010 10C during regular operation: table 7+8 in case of short-circuit: table 12 short-circuit duration max 5s |
Application
For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks.
The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.
Type Designation Codes
X | insulation made of cross-linked polyethylene (XLPE) |
K | screen made of copper |
D | longitudinally watertight in the screen section |
T | outer sheath made of polyethylene (PE) |
Y | 3 single-core cables, stranded |
T | common protective sheath |
Cu |
copper |
rm | round, stranded |
Additional Informations
Design according to customer specifications
Design with improved properties on request
Order Example
XKDT-YT 3 x 1 x 150 Curm/35 20/12 kV
BayEnergy® Medium voltage cables, XLPE insulation, Cu screen, PE sheath, 3-cores (stranded)
XKDT-YT
3-cores, copper, overall sheath based on DIN VDE 0276-620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.