Print Icon

BayEnergy® Medium voltage cables, XLPE insulation, Cu screen, PE sheath, 3-cores (stranded)

XKDT-YT

3-cores, aluminium, overall sheath based on DIN VDE 0276-620


DT136_en
RoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig36-Längswasserdicht53-Verlegung -20

 


Standards

Based on DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Al conductor, round, stranded, compressed  
Extruded inner conductive layer  
Insulation made of cross-linked PE  
Extruded outer conductive layer  
Screen made of Cu wires, with Cu counter helix  
Outer sheath made of halogen-free, robust PE  
Wear-resistant cable marking
2 red longitudinal strips, manufacturer, cable designation, year of manufacture, metre marking
 
3 single-core cables, stranded  
Common protective sheath  
Rated voltage kV 12/20
Testing voltage kV 30
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7+8
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

X insulation made of cross-linked polyethylene (XLPE)
K screen made of copper
D longitudinally watertight in the screen section
T sheath made of thermoplastic (PE)
Y 3 single-core cables, stranded
T common protective sheath

Al

aluminium
rm round, stranded

Additional Informations

Design according to customer specifications
Design with improved properties on request

Order Example

XKDT-YT  3 x 1 x 300 Alrm/35 Cu 12/20 kV


Print Icon

BayEnergy® Medium voltage cables, XLPE insulation, Cu screen, PE sheath, 3-cores (stranded)

XKDT-YT

3-cores, aluminium, overall sheath based on DIN VDE 0276-620

Product Bayka Order No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
mm kg/km kA daN min. mm min. mm  
XKDT-YT       3x1x 95 Alrm/16  12/20 kV 9754035 75 3540 8.90 840 760 920
XKDT-YT       3x1x150 Alrm/25  12/20 kV 9754040 81 4635 14.10 1350 830 1000
XKDT-YT       3x1x240 Alrm/35  12/20 kV 9754030 92 6394 22.60 2160 940 1130
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.