Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS2Y

6/10 kV acc. to DIN VDE 0276-620


BT10_N2XS2Y_de
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

optional

Verlegung -25 -30 -40 optional

Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 6/10
Testing voltage kV 15
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS2Y 1 x 150 RM/25 6/10 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS2Y

6/10 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XS2Y     1x50 RM/16   6/10kV 4770200 662 26 1050 7.15 250 195 390
N2XS2Y     1x70 RM/16   6/10kV 4760000 854 28 1200 10.01 350 210 420
N2XS2Y     1x95 RM/16   6/10kV 4760100 1094 29 1500 13.59 475 220 440
N2XS2Y    1x120 RM/16   6/10kV 4760200 1334 31 1750 17.16 600 235 470
N2XS2Y    1x150 RM/16   6/10kV 4760300 1622 32 2000 21.45 750 240 480
N2XS2Y    1x150 RM/25   6/10kV 4760400 1723 32 2100 21.45 750 240 480
N2XS2Y    1x185 RM/16   6/10kV 4760500 1958 34 2350 26.46 925 255 510
N2XS2Y    1x185 RM/25   6/10kV 4760600 2059 34 2450 26.46 925 255 510
N2XS2Y    1x240 RM/16   6/10kV 4760700 2486 36 2900 34.32 1200 270 540
N2XS2Y    1x240 RM/25   6/10kV 4760800 2587 36 3000 34.32 1200 270 540
N2XS2Y    1x300 RM/25   6/10kV 4760900 3163 39 3600 42.90 1500 290 580
N2XS2Y    1x400 RM/35   6/10kV 4761000 4234 42 4500 57.20 2000 315 630
N2XS2Y    1x500 RM/35   6/10kV 4761100 5194 45 5500 71.50 2500 340 680
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.