Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS(F)2Y

6/10 kV acc. to DIN VDE 0276-620


BT111_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig36-Längswasserdicht23-Halogenfrei53-Verlegung -20

optional

Verlegung -25 -30 -40 optional

Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 6/10
Testing voltage kV 15
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
F cables longitudinally watertight in the screen section
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS(F)2Y 1 x 150 RM/25 6/10 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS(F)2Y

6/10 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XS(F)2Y     1x35 RM/16       6/10 kV 4763020 518 25 1000 5.01 175 190 380
N2XS(F)2Y     1x50 RM/16       6/10 kV 4763000 662 27 1120 7.15 250 205 410
N2XS(F)2Y     1x70 RM/16       6/10 kV 4763100 854 29 1400 10.01 350 220 440
N2XS(F)2Y     1x95 RM/16       6/10 kV 4763200 1094 30 1650 13.59 475 225 450
N2XS(F)2Y    1x120 RM/16       6/10 kV 4763300 1334 31 2000 17.16 600 235 470
N2XS(F)2Y    1x150 RM/16       6/10 kV 4763400 1622 33 2300 21.45 750 250 500
N2XS(F)2Y    1x150 RM/25       6/10 kV 4763500 1723 33 2400 21.45 750 250 500
N2XS(F)2Y    1x185 RM/16       6/10 kV 4771800 1958 35 2550 26.46 925 265 530
N2XS(F)2Y    1x185 RM/25       6/10 kV 4771900 2059 35 2650 26.46 925 265 530
N2XS(F)2Y    1x240 RM/16       6/10 kV 4763600 2486 37 3150 34.32 1200 280 560
N2XS(F)2Y    1x240 RM/25       6/10 kV 4772000 2587 37 3250 34.32 1200 280 560
N2XS(F)2Y    1x300 RM/25       6/10 kV 4763700 3163 39 3800 42.90 1500 295 590
N2XS(F)2Y    1x400 RM/35       6/10 kV 4729700 4234 43 4800 57.20 2000 320 640
N2XS(F)2Y    1x500 RM/35       6/10 kV 4763800 5194 46 5950 71.50 2500 345 690
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.