Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS(F)2Y

18/30 kV acc. to DIN VDE 0276-620


BT113_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig36-Längswasserdicht23-Halogenfrei53-Verlegung -20

 


Standards

See DIN VDE 0276-620.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 18/30
Testing voltage kV 47
Cable temperature ºC
during laying (min)
after laying (max)

-20
  +90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 620 S2:2010 10C
during regular operation: table 7-10
in case of short-circuit: table 12
short-circuit duration max 5s
 

Application

For installation in open air, in the ground, for power stations, industry and distribution boards or subscriber networks. For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The cables are UV-resistant and particularly resistant due to the outer sheath made of robust PE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
F cables longitudinally watertight in the screen section
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS(F)2Y 1 x 150 RM/25 18/30 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PE sheath

N2XS(F)2Y

18/30 kV acc. to DIN VDE 0276-620

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XS(F)2Y    1x50 RM/16        18/30 kV 4729100 662 35 1300 7.15 250 265 530
N2XS(F)2Y    1x70 RM/16        18/30 kV 4729200 854 36 1600 10.01 350 270 540
N2XS(F)2Y    1x95 RM/16        18/30 kV 4729300 1094 38 1850 13.59 475 290 580
N2XS(F)2Y   1x120 RM/16        18/30 kV 4728000 1334 39 2150 17.16 600 295 590
N2XS(F)2Y   1x150 RM/25        18/30 kV 4728200 1723 40 2500 21.45 750 300 600
N2XS(F)2Y   1x185 RM/25        18/30 kV 4728400 2059 42 2900 26.46 925 315 630
N2XS(F)2Y   1x185 RM/35        18/30 kV 4728300 2170 42 3050 26.46 925 315 630
N2XS(F)2Y   1x240 RM/25        18/30 kV 4728600 2587 44 3500 34.32 1200 330 660
N2XS(F)2Y   1x300 RM/25        18/30 kV 4728900 3163 46 4100 42.90 1500 345 690
N2XS(F)2Y   1x400 RM/35        18/30 kV 4730300 4234 49 5050 57.20 2000 370 740
N2XS(F)2Y   1x500 RM/35        18/30 kV 4730320 5194 53 6100 71.50 2500 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.