BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-O

1-2-cores acc. to DIN VDE 0276


AT101_NYY-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17 short-circuit duration max 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1). The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYY-O 1x400 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-O

1-2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYY-O         1x4 RE   0,6/1kV 4097100 38 8.5 130 0.46 20 70 140
NYY-O         1x6 RE   0,6/1kV 4040200 58 9 145 0.69 30 70 140
NYY-O        1x10 RE   0,6/1kV 4042300 96 10 190 1.15 50 75 150
NYY-O        1x16 RE   0,6/1kV 4040300 154 11 255 1.84 80 80 160
NYY-O        1x25 RM   0,6/1kV 4040400 240 13 375 2.88 125 100 200
NYY-O        1x35 RM   0,6/1kV 4040500 336 14 475 4.03 175 110 210
NYY-O        1x50 RM   0,6/1kV 4040600 480 15 615 5.75 250 120 240
NYY-O        1x70 RM   0,6/1kV 4040700 672 17 835 8.05 350 135 270
NYY-O        1x95 RM   0,6/1kV 4040800 912 19 1110 10.93 475 150 300
NYY-O       1x120 RM   0,6/1kV 4040900 1152 21 1355 13.80 600 160 320
NYY-O       1x150 RM   0,6/1kV 4041000 1440 23 1650 17.25 750 175 350
NYY-O       1x185 RM   0,6/1kV 4041100 1776 25 2025 21.28 925 190 380
NYY-O       1x240 RM   0,6/1kV 4041200 2304 27 2605 27.60 1200 210 420
NYY-O       1x300 RM   0,6/1kV 4041300 2880 30 3230 34.50 1500 235 470
NYY-O       1x400 RM   0,6/1kV 4040100 3840 33 4095 46.00 2000 255 510
NYY-O       1x500 RM   0,6/1kV 4041400 4800 37 5175 51.50 2500 285 570
NYY-O       1x630 RM   0,6/1kV 4042200 6048 43 6615 64.89 3150 325 650
NYY-O       2x1,5 RE   0,6/1kV 4042604 29 12 215 0.17 15 80 160
NYY-O       2x2,5 RE   0,6/1kV 4041514 48 13 250 0.29 25 85 170
NYY-O         2x4 RE   0,6/1kV 4041604 77 15 340 0.46 40 90 180
NYY-O         2x6 RE   0,6/1kV 4041704 115 16 410 0.69 60 95 190
NYY-O         2x6 RM   0,6/1kV 4044104 115 17 445 0.69 60 100 200
NYY-O        2x10 RE   0,6/1kV 4057904 192 17 535 1.15 100 110 220
NYY-O        2x16 RE   0,6/1kV 4041904 307 19 705 1.84 160 120 240
NYY-O        2x25 RM   0,6/1kV 4042004 480 24 1105 2.88 250 150 300
NYY-O        2x35 RM   0,6/1kV 4058004 672 25 1330 4.03 350 155 310
NYY-O        2x50 RM   0,6/1kV 4058104 960 29 1745 5.75 500 175 350
NYY-O        2x70 RM   0,6/1kV 4002704 1344 32 2345 8.05 700 200 400
NYY-O       2x120 RM   0,6/1kV 4002004 2390 41 3775 13.80 1200 245 490
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.