Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

4-cores with control core acc. to DIN VDE 0276


AT10_11_NYY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276 part 603 / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYY-J 4x120 SM + 1x1,5 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

4-cores with control core acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYY-J       4x10 RE + 1x1,5 RE    0,6/1 kV 4026124 400 20 800 1.15 200 120 240
NYY-J       4x25 RM + 1x1,5 RE    0,6/1 kV 4036904 974 28 1680 2.88 500 170 340
NYY-J       4x35 SM + 1x1,5 RE    0,6/1 kV 4034504 1358 28 1935 4.03 700 170 340
NYY-J       4x50 SM + 1x1,5 RE    0,6/1 kV 4034904 1934 31 2550 5.75 1000 195 390
NYY-J       4x70 SM + 1x1,5 RE    0,6/1 kV 4034604 2702 36 3485 8.05 1400 220 440
NYY-J       4x95 SM + 1x1,5 RE    0,6/1 kV 4034704 3662 40 4625 10.93 1900 250 500
NYY-J      4x120 SM + 1x1,5 RE    0,6/1 kV 4034104 4622 44 5745 13.80 2400 270 540
NYY-J      4x150 SM + 1x1,5 RE    0,6/1 kV 4034204 5774 48 7000 17.25 3000 295 590
NYY-J      4x185 SM + 1x1,5 RE    0,6/1 kV 4034304 7118 53 8700 21.28 3700 325 650
NYY-J      4x240 SM + 1x1,5 RE    0,6/1 kV 4034404 9230 60 11130 27.60 4800 360 720
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.