Download IconPrint Icon

BayEnergy® CPR Eca Power cables, PVC insulation, PVC sheath

NYY-J

3 1/2-cores acc. to DIN VDE 0276


AT10_11_NYY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276 part 603 / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinylchloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Order Example

NYY-J 3x120 SM/70 RM 0,6/1 kV


Print Icon

BayEnergy® CPR Eca Power cables, PVC insulation, PVC sheath

NYY-J

3 1/2-cores acc. to DIN VDE 0276

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
BayEnergy® CPR Eca
NYY-J         3x25 RM/16 RE    0,6/1 kV
Eca 4023704 874 27 1630 2.88 455 170 340
BayEnergy® CPR Eca
NYY-J         3x35 SM/16 RE    0,6/1 kV
Eca 4024804 1162 28 1810 4.03 605 170 340
BayEnergy® CPR Eca
NYY-J         3x50 SM/25 RM    0,6/1 kV
Eca 4024904 1680 31 2370 5.75 875 195 390
BayEnergy® CPR Eca
NYY-J         3x70 SM/35 SM    0,6/1 kV
Eca 4025104 2352 34 3315 8.05 1225 210 420
BayEnergy® CPR Eca
NYY-J         3x95 SM/50 SM    0,6/1 kV
Eca 4025204 3216 39 4150 0.00 0 0 0
BayEnergy® CPR Eca
NYY-J         3x95 SM/50 RM    0,6/1 kV
Eca 4048104 3216 40 4280 10.93 1675 250 500
BayEnergy® CPR Eca
NYY-J        3x120 SM/70 SM    0,6/1 kV
Eca 4025304 4128 42 5200 0.00 0 0 0
BayEnergy® CPR Eca
NYY-J        3x120 SM/70 RM    0,6/1 kV
Eca 4025324 4128 44 5405 13.80 2150 265 530
BayEnergy® CPR Eca
NYY-J        3x150 SM/70 SM    0,6/1 kV
Eca 4025404 4992 47 6200 0.00 0 0 0
BayEnergy® CPR Eca
NYY-J        3x150 SM/70 RM    0,6/1 kV
Eca 4025414 4992 48 6400 17.25 2600 295 590
BayEnergy® CPR Eca
NYY-J        3x185 SM/95 SM    0,6/1 kV
Eca 4048404 6240 52 7800 21.28 3250 315 630
BayEnergy® CPR Eca
NYY-J        3x185 SM/95 RM    0,6/1 kV
Eca 4025504 6240 53 7960 21.28 3250 320 640
BayEnergy® CPR Eca
NYY-J       3x240 SM/120 SM    0,6/1 kV
Eca 4048604 8064 59 9000 27.60 4200 355 710
BayEnergy® CPR Eca
NYY-J       3x240 SM/120 RM    0,6/1 kV
Eca 4025604 8064 59 10210 27.60 4200 360 720
BayEnergy® CPR Eca
NYY-J       3x300 SM/150 RM    0,6/1 kV
Eca 4027904 10080 65 12570 34.50 5250 400 800
BayEnergy® CPR Eca
NYY-J       3x400 SM  0,6/1kV
Eca 4023914 11426 66 13200 41.20 6000 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.