Print Icon

BayEnergy® Railway power cables, copper

N2XSY / N2XS2Y / N2XS(F)2Y

Railway power cables 1kV acc. to DIN VDE 0271


AT361_N2XS_Bahnstrom_Cu_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!50-Verlegung -5

 


Standards

DIN VDE 0271.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Cables with PVC sheath are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1).
Cables with PE sheath are UV-resistant, however not flame retardant.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying
PVC-insulated cables (max)
XLPE-insulated cables (max)


-5

+70
+90

Max permissible operating temperature
(conductor) °C
PVC-insulated cables
XLPE-insulated cables


+70
+90
Short-circuit temperature °C
PVC-insulated cables
XLPE-insulated cables

+160
+250

Current carrying capacity, PVC-insulated cables
acc. to HD 603 S1-1994 3G
Current carrying capacity, XLPE-insulated cables
acc. to HD 603 S1-1994 5G

during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s

 

Application

Cables for special applications, e.g. as a single-core railway traction current cable for direct current and alternating current. Also as a return current cable in direct current systems up to 0.6/1 KV.

Preferably for connections in overhead lines and rails, for laying in pipe conduits and trough channels and directly in the ground.

The regulations and standards of the transport services apply for the selection of railway traction current cables.

Type Designation Codes

N cables acc. to standard
2X insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
(F) longitudinally watertight in the screen section
Y outer sheath made of polyvinyl chloride (PVC)
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XSY      1x400 RM/35    0,6/1 kV (A-SW)
N2XS2Y    1x400 RM/35  0,6/1 kV (A-SW)
N2XS(F)2Y 1x400 RM/35   0,6/1 kV (A-SW)


Print Icon

BayEnergy® Railway power cables, copper

N2XSY / N2XS2Y / N2XS(F)2Y

Railway power cables 1kV acc. to DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XSY    1x150 RM/16   0,6/1kV  (A-SW) 4426730 1622 24 1865 21.45 750 180 360
N2XSY    1x150 RM/25   0,6/1kV  (A-SW) 4426740 1723 25 1970 21.45 750 190 380
N2XSY    1x185 RM/16   0,6/1kV  (A-SW) 4426750 1958 16 2220 24.46 925 200 400
N2XSY    1x185 RM/25   0,6/1kV  (A-SW) 4426760 2059 27 2330 26.46 925 200 400
N2XSY    1x240 RM/25   0,6/1kV  (A-SW) 4426770 2587 29 2885 34.32 1200 220 440
N2XSY    1x300 RM/25   0,6/1kV  (A-SW) 4466650 3163 32 3475 42.90 1500 240 480
N2XSY    1x400 RM/35   0,6/1kV  (A-SW) 4426780 4234 35 4590 57.20 2000 270 540
N2XSY    1x500 RM/35   0,6/1kV  (A-SW) 4426720 5194 39 5600 71.50 2500 290 580
N2XSY    1x500 RM/50   0,6/1kV  (A-SW) 4426710 5360 40 5770 71.50 2500 300 600
N2XS2Y    1x150 RM/16  0,6/1kV  (A-SW) 4436000 1622 25 1780 21.45 750 190 380
N2XS2Y    1x150 RM/25  0,6/1kV  (A-SW) 4436010 1723 25 1880 21.45 750 190 380
N2XS2Y    1x185 RM/16  0,6/1kV  (A-SW) 4436020 1958 27 2135 26.46 925 200 400
N2XS2Y    1x185 RM/25  0,6/1kV  (A-SW) 4436030 2059 27 2240 26.46 925 200 400
N2XS2Y    1x240 RM/25  0,6/1kV  (A-SW) 4436040 2587 30 2780 34.32 1200 220 440
N2XS2Y    1x300 RM/25  0,6/1kV  (A-SW) 4436050 3163 32 3360 42.90 1500 240 480
N2XS2Y    1x300 RM/35  0,6/1kV  (A-SW) 4436055 3274 32 3470 42.90 1500 240 480
N2XS2Y    1x400 RM/35  0,6/1kV  (A-SW) 4421910 4234 35 4455 57.20 2000 270 540
N2XS2Y    1x500 RM/35  0,6/1kV  (A-SW) 4426700 5194 39 5445 71.50 2500 300 600
N2XS2Y    1x630 RM/35  0,6/1kV  (A-SW) 4436090 6442 44 6705 90.09 3150 330 660
N2XS(F)2Y     1x150 RM/16      0,6/1 kV   (A-SW) 4413020 1622 25 1650 21.45 750 190 380
N2XS(F)2Y     1x150 RM/25      0,6/1 kV   (A-SW) 4413030 1723 25 1890 21.45 750 190 380
N2XS(F)2Y     1x185 RM/16      0,6/1 kV   (A-SW) 4413040 1958 27 2140 26.46 925 200 400
N2XS(F)2Y     1x185 RM/25      0,6/1 kV   (A-SW) 4413050 2059 27 2245 26.46 925 210 420
N2XS(F)2Y     1x240 RM/25      0,6/1 kV   (A-SW) 4413010 2587 30 2815 34.32 1200 230 460
N2XS(F)2Y     1x300 RM/25      0,6/1 kV   (A-SW) 4413060 3163 32 3405 42.90 1500 240 480
N2XS(F)2Y     1x400 RM/35      0,6/1 kV   (A-SW) 4413070 4234 36 4510 57.20 2000 270 540
N2XS(F)2Y     1x500 RM/35      0,6/1 kV   (A-SW) 4413000 5194 40 5525 71.50 2500 300 600
N2XS(F)2Y     1x500 RM/50      0,6/1 kV   (A-SW) 4413100 5360 40 5680 71.50 2500 300 600
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.