Standards

DIN VDE 0276-627 part 4H / HD 627 S1 and IEC 60502-1, cores with black numbering printed.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYY-J 5x2,5 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

multicore acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYY-J       7x1,5 RE   0,6/1kV 4088200 101 15 370 0.17 53 100 200
NYY-J       7x2,5 RE   0,6/1kV 4089900 168 17 460 0.29 88 100 200
NYY-J         7x4 RE   0,6/1kV 4091400 269 19 660 0.46 140 120 240
(N)YY-J       7x6 RE   0,6/1kV 4092200 403 21 830 0.69 210 130 260
(N)YY-J      7x10 RE   0,6/1kV 4099000 672 23 1170 1.15 350 140 280
NYY-J       8x1,5 RE   0,6/1kV 4088300 115 16 420 0.17 60 100 200
NYY-J       8x2,5 RE   0,6/1kV 4090100 192 18 520 0.29 100 110 220
NYY-J      10x1,5 RE   0,6/1kV 4088500 144 18 500 0.17 75 110 220
NYY-J      10x2,5 RE   0,6/1kV 4090200 240 20 630 0.29 125 120 240
NYY-J        10x4 RE   0,6/1kV 4092300 384 23 910 0.46 200 140 280
NYY-J      12x1,5 RE   0,6/1kV 4088600 173 19 550 0.17 90 120 240
NYY-J      12x2,5 RE   0,6/1kV 4090300 288 20 700 0.29 150 130 260
NYY-J        12x4 RE   0,6/1kV 4092400 461 24 1010 0.46 240 150 300
(N)YY-J      12x6 RE   0,6/1kV 4092500 691 26 1300 0.69 360 160 320
NYY-J      14x1,5 RE   0,6/1kV 4088700 202 20 610 0.17 105 120 240
NYY-J      14x2,5 RE   0,6/1kV 4090400 336 21 780 0.29 175 130 260
NYY-J        14x4 RE   0,6/1kV 4092700 538 25 1140 0.46 280 150 300
NYY-J      16x1,5 RE   0,6/1kV 4088800 230 21 680 0.17 120 130 260
NYY-J      16x2,5 RE   0,6/1kV 4090500 384 22 870 0.29 200 140 280
NYY-J      19x1,5 RE   0,6/1kV 4088900 274 21 750 0.17 143 130 260
NYY-J      19x2,5 RE   0,6/1kV 4090600 456 23 970 0.29 238 140 280
NYY-J        19x4 RE   0,6/1kV 4091800 730 28 1430 0.46 380 170 340
(N)YY-J      19x6 RE   0,6/1kV 4092600 1104 30 1880 0.69 570 180 360
NYY-J      21x1,5 RE   0,6/1kV 4089000 302 22 820 0.17 158 140 280
NYY-J      21x2,5 RE   0,6/1kV 4090800 504 24 1060 0.29 263 150 300
(N)YY-J      21x4 RE   0,6/1kV 4091700 806 29 1570 0.46 420 180 360
NYY-J      24x1,5 RE   0,6/1kV 4089100 346 24 920 0.17 180 150 300
NYY-J      24x2,5 RE   0,6/1kV 4090900 576 27 1200 0.29 300 160 320
(N)YY-J      24x4 RE   0,6/1kV 4091900 922 33 1840 0.46 480 200 400
NYY-J      27x1,5 RE   0,6/1kV 4088400 396 25 990 0.17 203 150 300
NYY-J      27x2,5 RE   0,6/1kV 4090700 636 27 1300 0.29 338 170 340
NYY-J      30x1,5 RE   0,6/1kV 4089200 432 26 1070 0.17 225 160 320
NYY-J      30x2,5 RE   0,6/1kV 4091000 720 28 1410 0.29 375 170 340
(N)YY-J      30x4 RE   0,6/1kV 4092100 1152 34 2180 0.46 600 210 420
NYY-J      33x1,5 RE   0,6/1kV 4089300 475 27 1160 0.17 248 160 320
NYY-J      33x2,5 RE   0,6/1kV 4013200 795 29 1530 0.29 413 180 360
NYY-J      40x1,5 RE   0,6/1kV 4089400 576 28 1340 0.17 300 170 340
NYY-J      40x2,5 RE   0,6/1kV 4091600 960 31 1800 0.29 500 190 380
(N)YY-J      40x4 RE   0,6/1kV 4091100 1510 39 2800 0.46 800 230 460
(N)YY-J      40x6 RE   0,6/1kV 4094000 2300 42 3720 0.69 1200 260 520
NYY-J      48x1,5 RE   0,6/1kV 4089500 692 31 1580 0.17 360 190 380
NYY-J      48x2,5 RE   0,6/1kV 4029500 1126 35 2160 0.29 600 210 420
NYY-J      52x1,5 RE   0,6/1kV 4089600 749 32 1680 0.17 390 190 380
NYY-J      52x2,5 RE   0,6/1kV 4091200 1248 36 2310 0.29 650 220 440
NYY-J      61x1,5 RE   0,6/1kV 4089700 878 34 1960 0.17 458 210 420
NYY-J      61x2,5 RE   0,6/1kV 4092000 1464 38 2650 0.29 763 230 460
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.