BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-O

3 1/2-cores acc. to DIN VDE 0276


AT104_NYY-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYY-O 3x150 SM/70 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-O

3 1/2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYY-O         3x25 RM/16 RE    0,6/1 kV 4044704 874 28 1630 2.88 375 170 340
NYY-O         3x35 SM/16 RE    0,6/1 kV 4044804 1162 28 1810 4.03 525 170 340
NYY-O         3x50 SM/25 RM    0,6/1 kV 4044904 1680 31 2370 5.75 750 190 380
NYY-O         3x70 SM/35 RM    0,6/1 kV 4045104 2352 36 3270 8.05 1050 215 430
NYY-O         3x70 SM/35 SM    0,6/1 kV 4095004 2352 34 3115 8.05 1050 210 420
NYY-O         3x95 SM/50 RM    0,6/1 kV 4045204 3216 40 4280 10.93 1425 245 490
NYY-O         3x95 SM/50 SM    0,6/1 kV 4095104 2736 39 4150 10.93 1425 235 470
NYY-O        3x120 SM/70 RM    0,6/1 kV 4045304 4128 44 5330 13.80 1800 265 530
NYY-O        3x120 SM/70 SM    0,6/1 kV 4045314 4128 43 5200 13.80 1800 265 530
NYY-O        3x150 SM/70 RM    0,6/1 kV 4045404 4992 48 6395 17.25 2250 295 590
NYY-O        3x150 SM/70 SM    0,6/1 kV 4045414 4320 47 6200 17.25 2250 280 560
NYY-O        3x185 SM/95 RM    0,6/1 kV 4045504 6240 53 7960 21.28 2775 320 640
NYY-O        3x185 SM/95 SM    0,6/1 kV 4096004 6240 51 7610 21.28 2775 305 610
NYY-O       3x240 SM/120 RM    0,6/1 kV 4045604 8064 59 10210 27.60 3600 360 720
NYY-O       3x240 SM/120 SM    0,6/1 kV 4045614 8064 59 9000 27.60 3600 360 720
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.