BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath

NYCY

with protective conductor acc. to DIN VDE 0276


AT131_NYCY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
C Concentric Cu-conductor
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYCY-J 3 x 2,5 RE/2,5 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath

NYCY

with protective conductor acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYCY-J   3x2,5 RE/2,5  0,6/1kV 4123104 104 15 320 0.29 38 90 180
NYCY-J   5x1,5 RE/1,5  0,6/1kV 4121604 95 16 345 0.17 38 100 200
NYCY-J   5x2,5 RE/2,5  0,6/1kV 4146804 152 16 420 0.29 63 105 210
NYCY-J     5x4 RE/4    0,6/1kV 4123004 238 19 600 0.46 100 120 240
NYCY-J     5x6 RE/6    0,6/1kV 4123404 355 21 765 0.69 150 135 270
NYCY-J     5x6 RE/16   0,6/1kV 4125204 462 22 860 0.69 150 135 270
NYCY-J   7x1,5 RE/2,5  0,6/1kV 4153500 133 16 410 0.17 53 105 210
NYCY-J  19x1,5 RE/4    0,6/1kV 4174900 320 23 785 0.17 144 140 280
NYCY-J  24x1,5 RE/10   0,6/1kV 4147110 466 26 1015 0.18 186 165 330
NYCY-J  24x2,5 RE/10   0,6/1kV 4167500 696 28 1290 0.29 302 175 350
NYCY-J  61x1,5 RE/10   0,6/1kV 4119100 998 36 2055 0.17 464 220 440
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.