Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-J

1-3-cores acc. to DIN VDE 0265


AT17_NYKY-J_en
VDE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optional

Standards

DIN VDE 0265 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, especially in applications where there is the influence of solvents, fuels, oils, gasoline or similar must be expected (e.g., refineries and gas stations).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
K lead sheath
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYKY-J 3x1,5 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-J

1-3-cores acc. to DIN VDE 0265

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NYKY-J      1x50 RM   0,6/1 kV 4335700 480 588 17 1150 5.75 250 130 260
NYKY-J      1x70 RM   0,6/1 kV 4335200 672 680 19 1440 8.05 350 140 280
NYKY-J      1x95 RM   0,6/1 kV 4335210 912 814 21 1810 10.93 475 160 320
NYKY-J     1x120 RM   0,6/1 kV 4335220 1152 969 23 2190 13.80 600 170 340
NYKY-J     1x150 RM   0,6/1 kV 4335230 1440 1068 24 2560 17.25 750 180 360
NYKY-J     1x185 RM   0,6/1 kV 4335240 1776 1276 27 3120 21.28 925 200 400
NYKY-J     1x240 RM   0,6/1 kV 4335250 2304 1447 30 3840 27.60 1200 220 440
NYKY-J     1x300 RM   0,6/1 kV 4335260 2880 1710 32 4680 34.50 1500 240 480
NYKY-J     3x1,5 RE   0,6/1 kV 4331304 43 427 14 660 0.17 23 90 180
NYKY-J     3x2,5 RE   0,6/1 kV 4334704 72 487 15 740 0.29 38 90 180
NYKY-J       3x4 RE   0,6/1 kV 4335004 115 555 17 920 0.46 60 100 200
NYKY-J       3x6 RE   0,6/1 kV 4335304 174 635 18 1060 0.69 90 110 220
NYKY-J      3x10 RE   0,6/1 kV 4335704 288 747 20 1290 1.15 150 120 240
NYKY-J      3x25 RM   0,6/1 kV 4338304 720 1344 27 2510 2.88 375 170 340
NYKY-J      3x35 SM   0,6/1 kV 4338404 1008 1297 28 2790 4.03 525 170 340
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.