Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-J

4-5-cores acc. to DIN VDE 0265


AT17_NYKY-J_en
VDE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

 


Standards

DIN VDE 0265 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (EN 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

 

For indoor and outdoor installation, in the ground, especially in applications where there is the influence of solvents, fuels, oils, gasoline or similar must be expected (e.g., refineries and gas stations).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
K lead sheath
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Order Example

NYKY-J 4x1,5 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-J

4-5-cores acc. to DIN VDE 0265

Product CPR DoP *) Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
BaySpecial®
NYKY-J     4x1,5 RE   0,6/1 kV
N/A 4331404 58 464 15 720 0.17 30 90 180
BaySpecial®
NYKY-J     4x2,5 RE   0,6/1 kV
N/A 4331904 96 530 16 820 0.29 50 100 200
BaySpecial®
NYKY-J       4x4 RE   0,6/1 kV
N/A 4334904 154 605 18 1050 0.46 80 110 220
BaySpecial®
NYKY-J       4x4 RE   0,6/1 kV  (bw)
N/A 4334901 0 0 16 870 0.46 80 100 200
BaySpecial®
NYKY-J       4x6 RE   0,6/1 kV
N/A 4335504 230 665 19 1200 0.69 120 120 240
BaySpecial®
NYKY-J      4x10 RE   0,6/1 kV
N/A 4335604 384 750 21 1500 1.15 200 130 260
BaySpecial®
NYKY-J      4x16 RE   0,6/1 kV
N/A 4336504 614 975 24 2050 1.84 320 150 300
BaySpecial®
NYKY-J      4x25 RM   0,6/1 kV
N/A 4336304 960 1290 29 2950 2.88 500 180 360
BaySpecial®
NYKY-J      4x35 SM   0,6/1 kV
N/A 4336704 1344 1340 31 3300 4.03 700 190 380
BaySpecial®
NYKY-J      4x35 SM   0,6/1 kV  (bw)
N/A 4336701 0 0 29 3040 4.03 700 180 360
BaySpecial®
NYKY-J      4x50 SM   0,6/1 kV
N/A 4343304 1920 1680 34 4220 5.75 1000 210 420
BaySpecial®
NYKY-J      4x50 SM   0,6/1 kV  (bw)
N/A 4343301 1920 1560 32 3760 5.75 1000 190 380
BaySpecial®
NYKY-J      4x70 SM   0,6/1 kV
N/A 4339904 2688 2020 39 5460 8.05 1400 240 480
BaySpecial®
NYKY-J      4x70 SM   0,6/1 kV  (bw)
N/A 4339901 2688 1893 36 4910 8.05 1400 220 440
BaySpecial®
NYKY-J      4x95 SM   0,6/1 kV
N/A 4340004 3648 2440 44 7080 10.93 1900 270 540
BaySpecial®
NYKY-J      4x95 SM   0,6/1 kV  (bw)
N/A 4340001 3648 2369 41 6430 10.93 1900 250 500
BaySpecial®
NYKY-J     4x120 SM   0,6/1 kV
N/A 4340304 4608 2700 48 8580 13.80 2400 290 580
BaySpecial®
NYKY-J     4x120 SM   0,6/1 kV  (bw)
N/A 4340301 4608 2624 45 7730 13.80 2400 270 540
BaySpecial®
NYKY-J     4x150 SM   0,6/1 kV
N/A 4340404 5760 3530 52 10350 17.25 3000 320 640
BaySpecial®
NYKY-J     4x150 SM   0,6/1 kV  (bw)
N/A 4340401 5760 3283 49 9430 17.25 3000 300 600
BaySpecial®
NYKY-J     4x185 SM   0,6/1 kV
N/A 4340504 7104 4080 58 12550 21.28 3700 350 700
BaySpecial®
NYKY-J     4x240 SM   0,6/1 kV
N/A 4340604 9216 5230 64 16150 27.60 4800 390 780
BaySpecial®
NYKY-J     5x1,5 RE   0,6/1 kV
N/A 4331504 72 505 16 800 0.17 38 100 200
BaySpecial®
NYKY-J     5x2,5 RE   0,6/1 kV
N/A 4332004 120 580 17 920 0.29 63 100 200
BaySpecial®
NYKY-J       5x4 RE   0,6/1 kV
N/A 4335104 192 665 19 1180 0.46 100 120 240
BaySpecial®
NYKY-J       5x6 RE   0,6/1 kV
N/A 4344604 288 730 20 1370 0.69 150 120 240
BaySpecial®
NYKY-J       5x6 RE   0,6/1 kV  (bw)
N/A 4344601 0 0 19 1170 0.69 150 120 240
BaySpecial®
NYKY-J      5x10 RE   0,6/1 kV
N/A 4336004 480 930 23 1800 1.15 250 140 280
BaySpecial®
NYKY-J      5x16 RE   0,6/1 kV
N/A 4336604 768 1070 26 2350 1.84 400 160 320
BaySpecial®
NYKY-J      5x25 RM   0,6/1 kV
N/A 4336404 1272 1495 32 3420 2.88 625 190 380
BaySpecial®
NYKY-J      5x35 RM   0,6/1 kV
N/A 4336804 1780 1937 35 4320 4.03 875 210 420
BaySpecial®
NYKY-J      5x50 RM   0,6/1 kV
N/A 4336904 2400 2061 40 5490 5.75 1250 240 480
BaySpecial®
NYKY-J      5x70 RM   0,6/1 kV
N/A 4337104 3422 2756 45 7150 8.05 1750 270 540
BaySpecial®
NYKY-J      5x95 RM   0,6/1 kV
N/A 4337204 4560 3810 52 9830 10.93 2375 310 620
BaySpecial®
NYKY-J     4x95 RM/50 RM       0,6/1 kV
N/A 4340104 4252 3843 51 9295 10.93 2150 315 630
BaySpecial®
NYKY-J     5x120 RM   0,6/1 kV
N/A 4337404 5760 4312 57 11780 13.80 3000 340 680
BaySpecial®
NYKY-J     5x150 RM   0,6/1 kV
N/A 4337304 6827 5365 63 14370 17.25 3750 380 760
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR.Due to the flame-retardant outer sheath, it could be classified as Eca. If necessary, inform our sales team.