BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-J

3 1/2-cores acc. to DIN VDE 0276


AT32_N2XY-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl-chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-J 3x25 RM/16 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-J

3 1/2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XY-J      3x25 RM/16 RE      0,6/1 kV 4431014 874 26 1450 3.58 455 150 300
N2XY-J      3x35 RM/16 RE      0,6/1 kV 4431024 1162 28 1810 5.01 605 170 340
N2XY-J      3x50 SM/25 RM      0,6/1 kV 4462004 1680 30 2190 7.15 875 180 360
N2XY-J      3x70 SM/35 RM      0,6/1 kV 4462104 2352 34 3010 10.01 1225 210 420
N2XY-J      3x95 SM/50 RM      0,6/1 kV 4462204 3216 39 4010 13.59 1675 230 460
N2XY-J     3x120 SM/70 RM      0,6/1 kV 4462304 4128 43 5000 17.16 2150 260 520
N2XY-J     3x150 SM/70 RM      0,6/1 kV 4462404 4992 48 6050 21.45 2600 290 580
N2XY-J     3x185 SM/95 RM      0,6/1 kV 4462504 6240 53 7620 26.46 3250 320 640
N2XY-J     3x240 SM/120 RM     0,6/1 kV 4462604 8064 59 9800 34.32 4200 360 720
N2XY-J     3x300 SM/150 RM     0,6/1 kV 4405404 10080 64 12020 42.90 5250 390 780
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.