Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XCWH

4+1-cores (EMC+) acc. to DIN VDE 0276


AT434_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse23-Halogenfrei24-Flammwidrig26-Raucharm50-Verlegung -5

 


Standards

DIN VDE 0276-604-5G and IEC 60502,
halogen-free acc. to IEC 60754-1,
low gas corrosivity acc. to EN 50267,
low toxicity of gases acc. to DIN EN 50305,
low smoke density acc. to DIN EN 61034-2,
flame retardant acc. to IEC 60332-3.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU), RoHS Directive EU 2002/95/EC.
They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

The cables are halogen-free, fire retardant and low-smoke.
(FRNC - flame retardant, non corrosive, LSOH - low smoke, zero halogen).

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying
after laying

-5 to +50
-30 to +70
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 3G23
during regular operation: table 14+15
in case of short-circuit: table 17 short-circuit duration max 5s
 

Application

For indoor and outdoor installation, in open air (protected against direct sun light), however not directly in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage (see DIN VDE 0298-1).

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are conditionally UV-resistant and insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
2X core insulation made of cross-linked polyethylene (XLPE)
CW concentric conductor made of copper,
corrugated design (Ceander)
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCWH 4x150 SM/70 0,6/1 kV


Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XCWH

4+1-cores (EMC+) acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCWH   4x120 SM/120  0,6/1kV 4490084 5950 46 6480 17.16 2400 280 560
N2XCWH   4x150 SM/150  0,6/1kV 4490214 7202 51 7900 21.45 3000 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.