BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

4+1-cores (EMC+) acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627


AT33_N2XCY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

41-EMC+02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
2X core insulation made of cross-linked polyethylene (XLPE)
C concentric Cu-conductor, Cu-tape counter helix
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCY 4 x 240 SM/240 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

4+1-cores (EMC+) acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCY    4x1,5 RE/1,5  0,6/1kV 4440904 81 15 300 0.21 30 90 180
N2XCY    4x2,5 RE/2,5  0,6/1kV 4420504 128 15 360 0.36 50 90 180
N2XCY      4x4 RE/4    0,6/1kV 4424004 200 17 460 0.57 80 100 200
N2XCY      4x6 RE/6    0,6/1kV 4424014 297 18 580 0.86 120 110 220
N2XCY     4x10 RE/10   0,6/1kV 4424024 484 21 830 1.43 200 130 260
N2XCY     4x16 RE/16   0,6/1kV 4424034 796 23 1160 2.29 320 140 280
N2XCY    4x185 SM/185  0,6/1kV 4441774 9296 59 10020 26.46 3700 360 720
N2XCY    4x240 SM/240  0,6/1kV 4441794 12366 66 13000 34.32 4800 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.