Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XH-J

multicore acc. to DIN VDE 0276


AT416_N2XH-J_multi_en
RoHS_LogoREACH_LogoCE_Logo

 

08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse23-Halogenfrei24-Flammwidrig26-Raucharm50-Verlegung -5

 


Standards

DIN VDE 0276-627, part H7 and IEC 60502-1,
cores with black numbering printed,
low gas corrosivity acc. to EN 50267,
low toxicity of gases acc. to DIN EN 50305,
low smoke density acc. to DIN EN 61034-2,
flame retardant acc. to IEC 60332-3, EN 50266-2-4.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

The cables are halogen-free, fire retardant and low-smoke.
(FRNC - flame retardant, non corrosive, LSOH - low smoke, zero halogen).

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
+90
Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

Cable with improved behaviour in the event of fire.

For indoor and outdoor installation, in open air (protected against direct sun light), however not directly in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables made on standard
2X core insulation made of cross-linked polyethylene (XLPE)
H sheath made of thermoplastic, halogen-free polyolefin
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XH-J 7x2,5 RE 0,6/1 kV


Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XH-J

multicore acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XH-J     7x1,5 RE   0,6/1 kV 4422800 101 14 280 0.21 53 80 160
N2XH-J     7x2,5 RE   0,6/1 kV 4422600 168 15 360 0.36 88 90 180
N2XH-J       7x4 RE   0,6/1 kV 4422900 269 16 480 0.57 140 100 200
N2XH-J    10x1,5 RE   0,6/1 kV 4422810 144 16 380 0.21 75 100 200
N2XH-J    10x2,5 RE   0,6/1 kV 4422610 240 18 510 0.36 125 110 220
N2XH-J      10x4 RE   0,6/1 kV 4422910 384 20 680 0.57 200 120 240
N2XH-J    12x1,5 RE   0,6/1 kV 4422820 173 17 420 0.21 90 100 200
N2XH-J    12x2,5 RE   0,6/1 kV 4433300 288 19 570 0.36 150 110 220
N2XH-J      12x4 RE   0,6/1 kV 4422920 461 20 770 0.57 240 120 240
N2XH-J    14x1,5 RE   0,6/1 kV 4422830 202 18 480 0.21 105 110 220
N2XH-J    14x2,5 RE   0,6/1 kV 4422620 336 19 630 0.36 175 120 240
N2XH-J      14x4 RE   0,6/1 kV 4422930 538 21 860 0.57 280 130 260
N2XH-J    19x1,5 RE   0,6/1 kV 4422840 274 19 590 0.21 143 120 240
N2XH-J    19x2,5 RE   0,6/1 kV 4422630 456 21 790 0.36 238 130 260
N2XH-J      19x4 RE   0,6/1 kV 4422940 731 24 1100 0.57 380 140 280
N2XH-J    24x1,5 RE   0,6/1 kV 4422850 346 22 740 0.21 180 140 280
N2XH-J    24x2,5 RE   0,6/1 kV 4422640 576 25 1000 0.36 300 150 300
N2XH-J    30x1,5 RE   0,6/1 kV 4422860 432 24 860 0.21 225 140 280
N2XH-J    30x2,5 RE   0,6/1 kV 4422650 720 26 1170 0.36 375 160 320
(N)2XH-J    30x4 RE   0,6/1 kV 4422950 1152 29 1650 0.57 600 180 360
N2XH-J    40x1,5 RE   0,6/1 kV 4422870 576 26 1080 0.21 300 160 320
N2XH-J    40x2,5 RE   0,6/1 kV 4422660 960 29 1500 0.36 500 180 360
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.