BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCWY

3-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627


AT44_N2XCWY_en
electrosuisse_hochRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei46-Robust

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
  +90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17 short-circuit duration max 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature and higher loadability in the case of a short-circuit than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
CW concentric conductor made of copper, corrugated design (Ceander)
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCWY 3x35 SM/35   0,6/1kV


Print Icon

BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCWY

3-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCWY    3x10 RE/10   0,6/1kV 4441320 408 19 690 1.43 150 120 240
N2XCWY    3x16 RE/16   0,6/1kV 4441250 643 22 990 2.29 240 140 280
N2XCWY    3x25 RM/25   0,6/1kV 4441260 1045 26 1480 3.58 375 160 320
N2XCWY    3x25 RM/16   0,6/1kV 4441290 902 26 1375 3.58 375 170 340
N2XCWY    3x35 SM/16   0,6/1kV 4441434 1190 26 1580 5.01 525 160 320
N2XCWY    3x35 SM/35   0,6/1kV 4441444 1402 26 1760 5.01 525 160 320
N2XCWY    3x50 SM/25   0,6/1kV 4441454 1723 29 2080 7.15 750 180 360
N2XCWY    3x50 SM/50   0,6/1kV 4441464 2000 29 2300 7.15 750 180 360
N2XCWY    3x70 SM/35   0,6/1kV 4441474 2410 33 2820 10.01 1050 200 400
N2XCWY    3x70 SM/70   0,6/1kV 4441484 2796 33 3170 10.01 1050 200 400
N2XCWY    3x95 SM/50   0,6/1kV 4441504 3296 36 3800 13.59 1425 220 440
N2XCWY    3x95 SM/95   0,6/1kV 4441514 3791 37 4210 13.59 1425 230 460
N2XCWY   3x120 SM/70   0,6/1kV 4441524 4236 41 4750 17.16 1800 250 500
N2XCWY   3x120 SM/120  0,6/1kV 4441534 4786 41 5230 17.16 1800 250 500
N2XCWY   3x150 SM/70   0,6/1kV 4441544 5100 44 5690 21.45 2250 270 540
N2XCWY   3x185 SM/95   0,6/1kV 4441554 6383 49 7115 26.46 2775 300 600
N2XCWY   3x240 SM/120  0,6/1kV 4441574 8242 54 9150 34.32 3600 330 660
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.