Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

multicore acc. to DIN VDE 0276


AT316_N2XY-O_multi_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-627 part 4H / HD 627 S1 and IEC 60502-1,
cores with black numbering printed.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-O 14x2,5 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PVC sheath

N2XY-O

multicore acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XY-O     7x1,5 RE   0,6/1 kV 4420900 101 15 340 0.21 53 90 180
N2XY-O     7x2,5 RE   0,6/1 kV 4420800 168 16 420 0.36 88 100 200
N2XY-O       7x4 RE   0,6/1 kV 4420700 269 17 550 0.57 140 110 220
N2XY-O    10x1,5 RE   0,6/1 kV 4420910 144 18 450 0.21 75 110 220
N2XY-O    10x2,5 RE   0,6/1 kV 4420810 240 19 570 0.36 125 120 240
N2XY-O      10x4 RE   0,6/1 kV 4420710 384 21 750 0.57 200 130 260
N2XY-O    12x1,5 RE   0,6/1 kV 4420920 173 18 490 0.21 90 110 220
N2XY-O    12x2,5 RE   0,6/1 kV 4420820 288 20 630 0.36 150 120 240
N2XY-O      12x4 RE   0,6/1 kV 4420720 461 22 830 0.57 240 130 260
N2XY-O    14x1,5 RE   0,6/1 kV 4420930 202 19 540 0.21 105 120 240
N2XY-O    14x2,5 RE   0,6/1 kV 4420830 336 21 700 0.36 175 130 260
N2XY-O      14x4 RE   0,6/1 kV 4420730 538 23 940 0.57 280 140 280
N2XY-O    19x1,5 RE   0,6/1 kV 4420940 274 21 650 0.21 143 130 260
N2XY-O    19x2,5 RE   0,6/1 kV 4420840 456 23 860 0.36 238 140 280
N2XY-O      19x4 RE   0,6/1 kV 4420740 731 25 1170 0.57 380 150 300
N2XY-O    24x1,5 RE   0,6/1 kV 4420950 346 23 800 0.21 180 140 280
N2XY-O    24x2,5 RE   0,6/1 kV 4420850 576 26 1060 0.36 300 160 320
N2XY-O    30x1,5 RE   0,6/1 kV 4420960 432 25 920 0.21 225 150 300
N2XY-O    30x2,5 RE   0,6/1 kV 4420860 720 27 1240 0.36 375 160 320
N2XY-O    40x1,5 RE   0,6/1 kV 4420970 576 27 1150 0.21 300 170 340
N2XY-O    40x2,5 RE   0,6/1 kV 4420870 960 30 1580 0.36 500 180 360
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.