BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

1-core acc. to DIN VDE 0276


AT34_N2X2Y-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

04-Rohrverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Order Example

N2X2Y-O 1x25 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

1-core acc. to DIN VDE 0276

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2X2Y-O      1x6 RE   0,6/1 kV N/A 4400510 58 8.5 100 0.86 30 70 140
N2X2Y-O     1x10 RE   0,6/1 kV N/A 4400520 96 9.5 145 1.43 50 70 140
N2X2Y-O     1x16 RE   0,6/1 kV N/A 4400530 154 10.5 205 2.29 80 80 160
N2X2Y-O     1x25 RM   0,6/1 kV N/A 4400540 240 12.5 310 3.58 125 100 200
N2X2Y-O     1x35 RM   0,6/1 kV N/A 4400550 336 30 400 5.01 175 100 200
N2X2Y-O     1x50 RM   0,6/1 kV N/A 4400560 480 15 515 7.15 250 110 220
N2X2Y-O     1x70 RM   0,6/1 kV N/A 4415310 643 17 420 10.01 350 130 260
N2X2Y-O     1x95 RM   0,6/1 kV N/A 4400580 912 80 97 13.59 475 140 280
N2X2Y-O    1x120 RM   0,6/1 kV N/A 4406300 1152 20 1200 17.16 600 150 300
N2X2Y-O    1x150 RM   0,6/1 kV N/A 4400590 1440 22 1470 21.45 750 170 340
N2X2Y-O    1x185 RM   0,6/1 kV N/A 4406400 1776 24 1820 26.46 925 180 360
N2X2Y-O    1x240 RM   0,6/1 kV N/A 4406410 2304 27 2360 34.32 1200 200 400
N2X2Y-O    1x300 RM   0,6/1 kV N/A 4426200 2880 29 2920 42.90 1500 220 440
N2X2Y-O    1x400 RM   0,6/1 kV N/A 4406420 3840 32 3780 57.20 2000 240 480
N2X2Y-O    1x500 RM   0,6/1 kV N/A 4406430 4800 36 4810 71.50 2500 270 540
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR