N2XH-O

3-cores acc. to DIN VDE 0276


AT402_N2XH-O_3x_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse23-Halogenfrei24-Flammwidrig26-Raucharm50-Verlegung -5

 


Standards

DIN VDE 0276-604 and IEC 60502-1,
low gas corrosivity acc. to EN 50267,
low toxicity of gases acc. to DIN EN 50305,
low smoke density acc. to DIN EN 61034-2,
flame retardant acc. to IEC 60332-3, EN 50266-2-4.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

The cables are halogen-free, fire retardant and low-smoke.
(FRNC - flame retardant, non corrosive, LSOH - low smoke, zero halogen).

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
+90
Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994
during regular operation: B1
in case of short-circuit: B2
short-circuit duration max 5s
 

Application

Cable with improved behaviour in the event of fire.

For indoor and outdoor installation, in open air (protected against direct sun light), however not directly in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
H sheath made of thermoplastic, halogen-free polyolefin
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Order Example

N2XH-O 3x50 SM 0,6/1 kV


Print Icon

BayEnergy® CPR Eca Halogen-free powercables with special fire performance

N2XH-O

3-cores acc. to DIN VDE 0276

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
BayEnergy® CPR Eca
N2XH-O     3x1,5 RE   0,6/1 kV
Eca 4432214 43 11 180 0.21 23 70 140
BayEnergy® CPR Eca
N2XH-O     3x2,5 RE   0,6/1 kV
Eca 4432204 72 12 220 0.36 38 70 140
BayEnergy® CPR Eca
N2XH-O       3x4 RE   0,6/1 kV
Eca 4432224 115 13 280 0.57 60 80 160
BayEnergy® CPR Eca
N2XH-O       3x6 RE   0,6/1 kV
Eca 4432234 173 14 360 0.86 90 90 180
BayEnergy® CPR Eca
N2XH-O      3x10 RE   0,6/1 kV
Eca 4432244 288 16 510 1.43 150 100 200
BayEnergy® CPR Eca
N2XH-O      3x16 RE   0,6/1 kV
Eca 4432254 461 18 720 2.29 240 110 220
BayEnergy® CPR Eca
N2XH-O      3x25 RM   0,6/1 kV
Eca 4432264 720 22 1110 3.58 375 140 280
BayEnergy® CPR
N2XH-O      3x35 SM   0,6/1 kV
4432274 1008 23 1330 5.01 525 140 280
BayEnergy® CPR
N2XH-O      3x50 SM   0,6/1 kV
4432284 1440 26 1740 7.15 750 160 320
BayEnergy® CPR
N2XH-O      3x70 SM   0,6/1 kV
4432294 2016 30 2360 10.01 1050 180 360
BayEnergy® CPR
N2XH-O      3x95 SM   0,6/1 kV
4407314 2736 33 3160 13.59 1425 200 400
BayEnergy® CPR
N2XH-O     3x120 SM   0,6/1 kV
4407324 3456 36 3880 17.16 1800 220 440
BayEnergy® CPR
N2XH-O     3x150 SM   0,6/1 kV
4407334 4320 40 4730 21.45 2250 240 480
BayEnergy® CPR
N2XH-O     3x185 SM   0,6/1 kV
4407344 5328 45 5900 26.46 2775 270 540
BayEnergy® CPR
N2XH-O     3x240 SM   0,6/1 kV
4407354 6912 50 7640 34.32 3600 300 600
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.