Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

3-cores acc. to DIN VDE 0276


AT34_N2X2Y-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-20
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Order Example

N2XY-O 3x35 SM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

3-cores acc. to DIN VDE 0276

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2X2Y-O    3x1,5 RE   0,6/1 kV N/A 4426004 43 13 185 0.21 23 80 160
N2X2Y-O    3x2,5 RE   0,6/1 kV N/A 4426014 72 13.5 225 0.36 38 80 160
N2X2Y-O      3x4 RE   0,6/1 kV N/A 4426024 115 14.5 285 0.57 60 90 180
N2X2Y-O      3x6 RE   0,6/1 kV N/A 4426034 173 15.5 370 0.86 90 100 200
N2X2Y-O     3x10 RE   0,6/1 kV N/A 4426044 288 17 520 1.43 150 110 220
N2X2Y-O     3x16 RE   0,6/1 kV N/A 4426054 461 19 720 2.29 240 120 240
N2X2Y-O     3x25 RM   0,6/1 kV N/A 4426064 720 24 1110 3.58 375 150 300
N2X2Y-O     3x35 SM   0,6/1 kV N/A 4426074 1008 24 1300 5.01 525 150 300
N2X2Y-O     3x50 SM   0,6/1 kV N/A 4426084 1440 27 1720 7.15 750 170 340
N2X2Y-O     3x70 SM   0,6/1 kV N/A 4426094 2016 31 2340 10.01 1050 190 380
N2X2Y-O     3x95 SM   0,6/1 kV N/A 4426104 2736 34 3160 13.59 1425 210 420
N2X2Y-O    3x120 SM   0,6/1 kV N/A 4426114 3456 38 3890 17.16 1800 230 460
N2X2Y-O    3x150 SM   0,6/1 kV N/A 4426124 4320 42 4800 21.45 2250 260 520
N2X2Y-O    3x185 SM   0,6/1 kV N/A 4426134 5328 47 5910 26.46 2775 280 560
N2X2Y-O    3x240 SM   0,6/1 kV N/A 4426144 6912 52 7670 34.32 3600 310 620
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR