Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

3 1/2-cores acc. to DIN VDE 0276


AT34_N2X2Y-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

optional

Verlegung -25 -30 -40 optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-20
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-O 3x35 RM/16 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

3 1/2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2X2Y-O     3x25 RM/16 RE      0,6/1 kV 4481504 874 26 1380 3.58 455 160 320
N2X2Y-O     3x35 RM/16 RE      0,6/1 kV 4481514 1162 28 1710 5.01 605 170 340
N2X2Y-O     3x50 SM/25 RM      0,6/1 kV 4481524 1680 29 2065 7.15 875 180 360
N2X2Y-O     3x70 SM/35 RM      0,6/1 kV 4481534 2352 34 2865 10.01 1225 210 420
N2X2Y-O     3x95 SM/50 RM      0,6/1 kV 4481544 3216 38 3845 13.59 1675 230 460
N2X2Y-O    3x120 SM/70 RM      0,6/1 kV 4481554 4128 42 4815 17.16 2150 260 510
N2X2Y-O    3x150 SM/70 RM      0,6/1 kV 4481564 4992 47 5455 21.45 2600 290 580
N2X2Y-O    3x185 SM/95 RM      0,6/1 kV 4481574 6240 53 7335 26.46 3250 320 640
N2X2Y-O    3x240 SM/120 RM     0,6/1 kV 4481584 8064 59 9445 34.32 4200 360 720
N2X2Y-O    3x300 SM/150 RM     0,6/1 kV 4481594 10080 64 11675 42.90 5250 390 780
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.