BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

4-5-cores acc. to DIN VDE 0276


AT34_N2X2Y-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-20
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

For indoor installation, taking into account that the PE sheath is halogen-free, however not flame retardant according DIN VDE 0472, part 804, test type B.

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-O 4x35 SM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

4-5-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2X2Y-O    4x1,5 RE   0,6/1 kV 4406004 58 13 200 0.21 30 80 160
N2X2Y-O    4x2,5 RE   0,6/1 kV 4406014 96 14 250 0.36 50 90 170
N2X2Y-O      4x4 RE   0,6/1 kV 4406024 154 15 340 0.57 80 100 180
N2X2Y-O      4x6 RE   0,6/1 kV 4406034 230 16 440 0.86 120 100 200
N2X2Y-O     4x10 RE   0,6/1 kV 4406044 403 18 630 1.43 200 110 220
N2X2Y-O     4x16 RE   0,6/1 kV 4406054 614 21 900 2.29 320 130 250
N2X2Y-O     4x16 RM   0,6/1 kV 4406064 614 22 950 2.29 320 140 270
N2X2Y-O     4x25 RM   0,6/1 kV 4406074 960 26 1420 3.58 500 160 320
N2X2Y-O     4x35 SM   0,6/1 kV 4429904 1344 27 1675 5.01 700 160 320
N2X2Y-O     4x50 SM   0,6/1 kV 4406084 1920 30 2200 7.15 1000 180 360
N2X2Y-O     4x70 SM   0,6/1 kV 4408404 2688 34 3045 10.01 1400 210 420
N2X2Y-O     4x95 SM   0,6/1 kV 4406094 3648 38 4095 13.59 1900 230 460
N2X2Y-O    4x120 SM   0,6/1 kV 4499104 4608 43 5120 17.16 2400 260 520
N2X2Y-O    4x150 SM   0,6/1 kV 4406104 5760 47 6270 21.45 3000 290 580
N2X2Y-O    4x185 SM   0,6/1 kV 4406114 7104 53 7785 26.46 3700 320 640
N2X2Y-O    4x240 SM   0,6/1 kV 4406124 9216 59 10090 34.32 4800 360 720
N2X2Y-O    5x1,5 RE   0,6/1 kV 4406204 72 14 240 0.21 38 90 170
N2X2Y-O    5x2,5 RE   0,6/1 kV 4406214 120 15 300 0.36 63 90 180
N2X2Y-O      5x4 RE   0,6/1 kV 4406224 192 16 400 0.57 100 100 200
N2X2Y-O      5x6 RE   0,6/1 kV 4406234 288 17 525 0.86 150 110 210
N2X2Y-O     5x10 RE   0,6/1 kV 4406244 480 20 770 1.43 250 120 240
N2X2Y-O     5x16 RE   0,6/1 kV 4406254 768 22 1100 2.29 400 140 270
N2X2Y-O     5x16 RM   0,6/1 kV 4406264 768 24 1160 2.29 400 150 290
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.