Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

multicore acc. to DIN VDE 0276


AT34_N2X2Y-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

optional

Verlegung -25 -30 -40 optional

Standards

DIN VDE 0276-627 part 4H / HD 627 S1 and IEC 60502-1,
cores with black numbering printed.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-20
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
2Y outer sheath made of high-density polyethylene (HDPE)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XY-O 19x2,5 RE RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-O

multicore acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius repeated Bending radius one-off
kg/km mm kg/km kA daN min. mm min. mm  
N2X2Y-O    7x1,5 RE   0,6/1 kV 4410100 101 15 275 0.21 53 180 90
N2X2Y-O    7x2,5 RE   0,6/1 kV 4410800 168 16 355 0.36 88 190 100
N2X2Y-O      7x4 RE   0,6/1 kV 4410700 269 17 485 0.57 140 210 110
N2X2Y-O   10x1,5 RE   0,6/1 kV 4410110 144 17 375 0.21 75 210 110
N2X2Y-O   10x2,5 RE   0,6/1 kV 4410810 240 19 490 0.36 125 230 120
N2X2Y-O     10x4 RE   0,6/1 kV 4410710 384 21 685 0.57 200 260 130
N2X2Y-O   12x1,5 RE   0,6/1 kV 4410120 173 18 415 0.21 90 220 110
N2X2Y-O   12x2,5 RE   0,6/1 kV 4410820 288 19 545 0.36 150 240 120
N2X2Y-O     12x4 RE   0,6/1 kV 4410720 461 22 770 0.57 240 260 130
N2X2Y-O   14x1,5 RE   0,6/1 kV 4410130 202 19 460 0.21 105 230 120
N2X2Y-O   14x2,5 RE   0,6/1 kV 4410830 336 20 610 0.36 175 250 130
N2X2Y-O     14x4 RE   0,6/1 kV 4410730 538 22 875 0.57 280 270 140
N2X2Y-O   19x1,5 RE   0,6/1 kV 4410140 274 20 565 0.21 143 250 130
N2X2Y-O   19x2,5 RE   0,6/1 kV 4410840 456 22 775 0.36 238 270 140
N2X2Y-O     19x4 RE   0,6/1 kV 4410740 730 25 1110 0.57 380 300 150
N2X2Y-O   24x1,5 RE   0,6/1 kV 4410150 346 23 710 0.21 180 280 140
N2X2Y-O   24x2,5 RE   0,6/1 kV 4410850 576 26 965 0.36 300 310 160
N2X2Y-O   30x1,5 RE   0,6/1 kV 4410160 432 24 830 0.21 225 300 150
N2X2Y-O   30x2,5 RE   0,6/1 kV 4410860 720 27 1140 0.36 375 330 170
N2X2Y-O   40x1,5 RE   0,6/1 kV 4410170 576 27 1050 0.21 300 330 170
N2X2Y-O   40x2,5 RE   0,6/1 kV 4410870 960 30 1460 0.36 500 360 180
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.