Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-J

multicore acc. to DIN VDE 0276


AT34_N2X2Y-O_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276-627 part 4H / HD 627 S1 and IEC 60502-1,
cores with black numbering printed.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-20
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
Y outer sheath made of polyvinyl chloride (PVC)
2Y outer sheath made of high-density polyethylene (PE)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Order Example

N2X2Y-O 19x2,5 RE RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, PE sheath

N2X2Y-J

multicore acc. to DIN VDE 0276

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2X2Y-J    7x1,5 RE   0,6/1 kV N/A 4422520 101 15 280 0.21 53 90 180
N2X2Y-J    7x2,5 RE   0,6/1 kV N/A 4421800 168 16 360 0.36 88 100 200
N2X2Y-J      7x4 RE   0,6/1 kV N/A 4421100 269 17 480 0.57 140 110 220
N2X2Y-J   10x1,5 RE   0,6/1 kV N/A 4422510 144 17 375 0.21 75 110 210
N2X2Y-J   10x2,5 RE   0,6/1 kV N/A 4421810 240 19 500 0.36 125 120 240
N2X2Y-J     10x4 RE   0,6/1 kV N/A 4421110 384 21 670 0.57 200 130 260
N2X2Y-J   12x1,5 RE   0,6/1 kV N/A 4422530 173 18 420 0.21 90 110 220
N2X2Y-J   12x2,5 RE   0,6/1 kV N/A 4421820 288 20 560 0.36 150 120 240
N2X2Y-J     12x4 RE   0,6/1 kV N/A 4421120 461 22 760 0.57 240 130 260
N2X2Y-J   14x1,5 RE   0,6/1 kV N/A 4422540 202 19 470 0.21 105 120 240
N2X2Y-J   14x2,5 RE   0,6/1 kV N/A 4421830 336 21 620 0.36 175 130 260
N2X2Y-J     14x4 RE   0,6/1 kV N/A 4421130 538 23 870 0.57 280 140 280
N2X2Y-J   19x1,5 RE   0,6/1 kV N/A 4422550 274 21 580 0.21 143 130 260
N2X2Y-J   19x2,5 RE   0,6/1 kV N/A 4421840 456 23 780 0.36 238 140 280
N2X2Y-J     19x4 RE   0,6/1 kV N/A 4421140 730 25 1090 0.57 380 150 300
N2X2Y-J   24x1,5 RE   0,6/1 kV N/A 4422560 346 24 720 0.21 180 140 280
N2X2Y-J   24x2,5 RE   0,6/1 kV N/A 4421850 576 26 970 0.36 300 160 320
N2X2Y-J   30x1,5 RE   0,6/1 kV N/A 4422570 432 25 850 0.21 225 150 300
N2X2Y-J   30x2,5 RE   0,6/1 kV N/A 4421860 720 27 1150 0.36 375 170 340
N2X2Y-J   40x1,5 RE   0,6/1 kV N/A 4422580 576 27 1060 0.21 300 170 340
N2X2Y-J   40x2,5 RE   0,6/1 kV N/A 4421870 960 30 1470 0.36 500 180 360
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR