Print Icon

BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XC2Y

1-3-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627


AT38_N2XC2Y_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU), RoHS Directive EU 2002/95/EC.

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-20
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are halogen-free, UV-resistant and particularly resistant due to the outer sheath made of HDPE.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
C Concentric Cu-conductor
2Y outer sheath made of high-density polyethylene (HDPE)
  cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XC2Y 4x4 RE/4 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XC2Y

1-3-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XC2Y     2x4 RE/4    0,6/1kV 4461324 123 14 275 0.57 40 85 170
N2XC2Y     2x6 RE/6    0,6/1kV 4461004 182 16 390 0.86 60 110 220
N2XC2Y    2x10 RE/10   0,6/1kV 4461014 312 18 545 1.43 100 120 240
N2XC2Y   3x2,5 RE/2,5  0,6/1kV 4461114 104 14 255 0.36 38 90 180
N2XC2Y     3x4 RE/4    0,6/1kV 4461124 161 15 335 0.57 60 100 200
N2XC2Y     3x6 RE/6    0,6/1kV 4461134 240 17 435 0.86 90 110 220
N2XC2Y    3x10 RE/10   0,6/1kV 4461144 400 19 625 1.43 150 120 240
N2XC2Y    3x16 RE/16   0,6/1kV 4461154 625 21 885 2.29 240 130 260
N2XC2Y    3x25 RM/16   0,6/1kV 4461164 902 26 1305 3.58 375 160 320
N2XC2Y    3x35 SM/16   0,6/1kV 4461174 1165 26 1495 5.01 525 160 320
N2XC2Y    3x50 SM/25   0,6/1kV 4461184 1690 29 1990 7.15 750 180 360
N2XC2Y    3x70 SM/35   0,6/1kV 4461194 2385 33 2720 10.01 1050 210 420
N2XC2Y    3x95 SM/50   0,6/1kV 4461204 3289 38 3675 13.59 1425 240 480
N2XC2Y   3x120 SM/70   0,6/1kV 4461214 4156 42 4575 17.16 1800 250 500
N2XC2Y   3x150 SM/70   0,6/1kV 4461224 5045 46 5560 21.45 2250 280 560
N2XC2Y   3x185 SM/95   0,6/1kV 4461234 6409 50 6935 26.46 2775 310 620
N2XC2Y   3x240 SM/120  0,6/1kV 4461244 8242 56 8910 34.32 3600 340 680
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.