Print Icon

BayEnergy® Power cables, XLPE insulation, Al-laminated PE sheath

(N)2X(L)2Y-J

1-core based on DIN VDE 0276-603, resp. VDE 0276-6


AT391_(N)2X(L)2Y-J_1x_en
RoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig38-Querwasserdicht23-Halogenfrei53-Verlegung -20

 


Standards

Based on DIN VDE 0276 part 603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-20
+90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration: max 5s
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature and higher loadability in the case of a short-circuit than comparable cable with PVC core insulation.

The cables are transversally watertight due to the laminated sheath.

The cables are halogen-free and UV-resistant as well as transversally watertight due to the laminated sheath.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
(L)2Y laminated sheath made of high-density polyethylene (HDPE) and Al tape
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

(N)2X(L)2Y-J 1 x 25 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, Al-laminated PE sheath

(N)2X(L)2Y-J

1-core based on DIN VDE 0276-603, resp. VDE 0276-6

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
(N)2X(L)2Y-J       1x50 RM     0,6/1 kV 4455010 504 16 560 7.15 250 120 240
(N)2X(L)2Y-J       1x70 RM     0,6/1 kV 4455020 1152 18 760 10.01 350 140 280
(N)2X(L)2Y-J       1x95 RM     0,6/1 kV 4455110 936 20 1010 13.59 475 150 300
(N)2X(L)2Y-J      1x120 RM     0,6/1 kV 4455120 1152 22 1250 17.16 600 160 320
(N)2X(L)2Y-J      1x150 RM     0,6/1 kV 4455130 1464 23 1520 21.45 750 180 360
(N)2X(L)2Y-J      1x185 RM     0,6/1 kV 4455140 1176 26 1880 26.46 925 190 380
(N)2X(L)2Y-J      1x240 RM     0,6/1 kV 4455150 2304 28 2420 34.32 1200 210 420
(N)2X(L)2Y-J      1x300 RM     0,6/1 kV 4455160 2880 30 2980 42.90 1500 230 460
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.