Download IconPrint Icon

BayEnergy® Power cables, XLPE insulation, Al-laminated PE sheath

(N)2X(L)2Y-J

4-5-cores based on DIN VDE 0276-603, resp. VDE 0276-6


AT39_N2X(L)2Y_e
RoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig38-Querwasserdicht23-Halogenfrei53-Verlegung -20

 


Standards

Based on DIN VDE 0276 part 603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-20
+90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration: max 5s
 

Application

For outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature and higher loadability in the case of a short-circuit than comparable cable with PVC core insulation.

The cables are transversally watertight due to the laminated sheath.

The cables are halogen-free and UV-resistant as well as transversally watertight due to the laminated sheath.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
(L)2Y laminated sheath made of high-density polyethylene (HDPE) and Al tape
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Additional Informations

The cable is for installation in the ground or outside structures and is therefore not subject to the CPR.
It cannot be classified as Eca or better.

Order Example

(N)2X(L)2Y-J 4 x 25 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, Al-laminated PE sheath

(N)2X(L)2Y-J

4-5-cores based on DIN VDE 0276-603, resp. VDE 0276-6

Product CPR DoP *) Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
(N)2X(L)2Y-J      4x1,5 RE     0,6/1 kV N/A 4450104 68 15 250 0.21 30 90 180
(N)2X(L)2Y-J      4x2,5 RE     0,6/1 kV N/A 4450404 106 16 300 0.36 50 100 200
(N)2X(L)2Y-J        4x4 RE     0,6/1 kV N/A 4451104 164 17 390 0.57 80 100 200
(N)2X(L)2Y-J        4x6 RE     0,6/1 kV N/A 4451204 240 18 490 0.86 120 110 220
(N)2X(L)2Y-J       4x10 RE     0,6/1 kV N/A 4454004 389 20 680 1.43 200 120 240
(N)2X(L)2Y-J       4x16 RE     0,6/1 kV N/A 4454204 619 22 950 2.29 320 130 260
(N)2X(L)2Y-J       4x25 RM     0,6/1 kV N/A 4454404 965 27 1440 3.58 500 160 320
(N)2X(L)2Y-J       4x35 RM     0,6/1 kV N/A 4455704 1349 29 1870 5.01 700 180 360
(N)2X(L)2Y-J       4x50 SM     0,6/1 kV N/A 4455314 1925 32 2320 7.15 1000 190 380
(N)2X(L)2Y-J       4x70 SM     0,6/1 kV N/A 4455804 2693 36 3170 10.01 1400 220 440
(N)2X(L)2Y-J       4x95 SM     0,6/1 kV N/A 4455904 3653 40 4230 13.59 1900 240 480
(N)2X(L)2Y-J      4x120 SM     0,6/1 kV N/A 4456004 4613 45 5250 17.16 2400 270 540
(N)2X(L)2Y-J      4x150 SM     0,6/1 kV N/A 4456104 5765 49 6410 21.45 3000 300 600
(N)2X(L)2Y-J      4x185 SM     0,6/1 kV N/A 4456204 7109 55 7970 26.46 3700 330 660
(N)2X(L)2Y-J      4x240 SM     0,6/1 kV N/A 4456304 9221 64 10650 34.32 4800 390 780
(N)2X(L)2Y-J      5x1,5 RE     0,6/1 kV N/A 4449904 77 16 280 0.21 38 100 200
(N)2X(L)2Y-J      5x2,5 RE     0,6/1 kV N/A 4450504 125 17 350 0.36 63 100 200
(N)2X(L)2Y-J        5x4 RE     0,6/1 kV N/A 4450604 197 18 450 0.57 100 110 220
(N)2X(L)2Y-J        5x6 RE     0,6/1 kV N/A 4450704 293 19 570 0.86 150 120 240
(N)2X(L)2Y-J       5x10 RE     0,6/1 kV N/A 4451304 485 21 810 1.43 250 130 260
(N)2X(L)2Y-J       5x16 RE     0,6/1 kV N/A 4451400 773 23 1150 2.29 400 150 300
(N)2X(L)2Y-J       5x16 RE     0,6/1 kV N/A 4451414 773 24 1140 2.29 400 140 280
(N)2X(L)2Y-J       5x25 RM     0,6/1 kV N/A 4451804 1205 31 1880 3.58 625 190 380
(N)2X(L)2Y-J       5x35 RM     0,6/1 kV N/A 4451700 1680 33 2355 5.01 875 248 495
(N)2X(L)2Y-J       5x35 RM     0,6/1 kV N/A 4451704 1685 33 2420 5.01 875 200 400
(N)2X(L)2Y-J       5x50 RM     0,6/1 kV N/A 4451710 2405 36 3105 7.15 1250 280 560
(N)2X(L)2Y-J       5x50 RM     0,6/1 kV N/A 4451714 2405 37 3130 7.15 1250 220 460
(N)2X(L)2Y-J       5x95 RM     0,6/1 kV N/A 4451734 4565 48 5820 13.59 2375 290 580
(N)2X(L)2Y-J      5x240 RM     0,6/1 kV N/A 4451744 11525 73 12750 34.32 6000 440 880
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) N/A (not applicable) Cable is not subject to the Construction Products Regulation CPR