Download IconPrint Icon

BayEnergy® Power cables, XLPE insulation, Al-laminated PE sheath

(N)2X(L)2Y-J

multicore based on DIN VDE 0276-603, resp. VDE 0276-6


AT39_N2X(L)2Y_e
RoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung20-UV-beständig38-Querwasserdicht23-Halogenfrei53-Verlegung -20

 


Standards

Based on DIN VDE 0276-627 part 4H / HD 627 S1 and IEC 60502-1,
cores with black numbering printed.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-20
+90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, in open air, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature and higher loadability in the case of a short-circuit than comparable cable with PVC core insulation.

The cables are transversally watertight due to the laminated sheath.

The cables are halogen-free and UV-resistant as well as transversally watertight due to the laminated sheath.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
(L)2Y laminated sheath made of high-density polyethylene (HDPE) and Al tape
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

(N)2X(L)2Y-J 10 x 2,5 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, Al-laminated PE sheath

(N)2X(L)2Y-J

multicore based on DIN VDE 0276-603, resp. VDE 0276-6

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
(N)2X(L)2Y-J      7x1,5 RE     0,6/1 kV 4441200 106 16 320 0.21 53 100 200
(N)2X(L)2Y-J      7x2,5 RE     0,6/1 kV 4452800 173 17 410 0.36 88 110 220
(N)2X(L)2Y-J        7x4 RE     0,6/1 kV 4454700 274 19 540 0.57 140 120 240
(N)2X(L)2Y-J     10x1,5 RE     0,6/1 kV 4441300 149 19 440 0.21 75 120 240
(N)2X(L)2Y-J     10x2,5 RE     0,6/1 kV 4453000 245 21 560 0.36 125 130 260
(N)2X(L)2Y-J       10x4 RE     0,6/1 kV 4453100 389 23 740 0.57 200 140 280
(N)2X(L)2Y-J       10x6 RE     0,6/1 kV 4453200 594 25 980 0.86 300 150 300
(N)2X(L)2Y-J     12x1,5 RE     0,6/1 kV 4441400 178 20 470 0.21 90 120 240
(N)2X(L)2Y-J     12x2,5 RE     0,6/1 kV 4452900 292 21 610 0.36 150 130 260
(N)2X(L)2Y-J       12x4 RE     0,6/1 kV 4453110 468 23 810 0.57 240 140 280
(N)2X(L)2Y-J     14x1,5 RE     0,6/1 kV 4441500 207 20 520 0.21 105 120 240
(N)2X(L)2Y-J     14x2,5 RE     0,6/1 kV 4446200 341 22 670 0.36 175 130 260
(N)2X(L)2Y-J       14x4 RE     0,6/1 kV 4454800 543 24 910 0.57 280 150 300
(N)2X(L)2Y-J     16x1,5 RE     0,6/1 kV 4442200 238 21 570 0.21 120 130 260
(N)2X(L)2Y-J     16x2,5 RE     0,6/1 kV 4446300 389 23 750 0.36 200 140 280
(N)2X(L)2Y-J       16x4 RE     0,6/1 kV 4453120 607 25 1030 0.57 320 150 300
(N)2X(L)2Y-J     19x1,5 RE     0,6/1 kV 4442300 279 22 630 0.21 143 130 260
(N)2X(L)2Y-J     19x2,5 RE     0,6/1 kV 4437900 461 24 840 0.36 238 150 300
(N)2X(L)2Y-J       19x4 RE     0,6/1 kV 4454900 735 26 1150 0.57 380 160 320
(N)2X(L)2Y-J     24x1,5 RE     0,6/1 kV 4442400 351 25 780 0.21 180 150 300
(N)2X(L)2Y-J     24x2,5 RE     0,6/1 kV 4455200 581 27 1040 0.36 300 170 340
(N)2X(L)2Y-J       24x4 RE     0,6/1 kV 4455000 927 30 1450 0.57 480 180 360
(N)2X(L)2Y-J     30x1,5 RE     0,6/1 kV 4441520 439 26 900 0.00 225 160 320
(N)2X(L)2Y-J     30x2,5 RE     0,6/1 kV 4421600 720 29 1220 0.36 375 170 340
(N)2X(L)2Y-J       30x4 RE     0,6/1 kV 4455100 1157 32 1720 0.57 600 190 380
(N)2X(L)2Y-J     40x1,5 RE     0,6/1 kV 4441530 583 29 1140 0.21 300 180 360
(N)2X(L)2Y-J     40x2,5 RE     0,6/1 kV 4425600 960 32 1550 0.36 500 190 380
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.