BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

1-2-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627


AT33_N2XCY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

 


Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
2X core insulation made of cross-linked polyethylene (XLPE)
C concentric Cu-conductor, Cu-tape counter helix
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCY 2 x 4 RE/4 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

1-2-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCY      1x6 RE/6    0,6/1kV 4424600 124 11 210 0.86 30 80 160
N2XCY     1x10 RE/10   0,6/1kV 4424610 202 12 300 1.43 50 90 180
N2XCY     1x16 RE/16   0,6/1kV 4424620 322 13 410 2.29 80 100 200
N2XCY     1x16 RM/16   0,6/1kV 4424630 322 13 420 2.29 80 100 200
N2XCY     1x25 RM/16   0,6/1kV 4424640 405 15 520 3.58 125 110 220
N2XCY     1x35 RM/16   0,6/1kV 4424650 504 16 620 5.01 175 120 240
N2XCY     1x50 RM/25   0,6/1kV 4424660 743 17 830 7.15 250 130 260
N2XCY     1x70 RM/35   0,6/1kV 4424670 1040 20 1130 10.01 350 150 300
N2XCY     1x95 RM/50   0,6/1kV 4424680 1437 22 1500 13.59 475 170 340
N2XCY    1x120 RM/70   0,6/1kV 4424690 1869 24 1930 17.16 600 180 360
N2XCY    1x150 RM/70   0,6/1kV 4424700 2175 26 2385 21.45 750 200 400
N2XCY    1x185 RM/95   0,6/1kV 4424710 2770 29 2820 26.46 925 220 440
N2XCY    1x240 RM/120  0,6/1kV 4424720 3562 32 3590 34.32 1200 240 480
N2XCY    1x300 RM/150  0,6/1kV 4424730 4511 35 4930 42.90 1500 260 520
N2XCY    2x1,5 RE/1,5  0,6/1kV 4441230 56 13 230 0.21 15 80 160
N2XCY    2x2,5 RE/2,5  0,6/1kV 4441100 80 14 280 0.36 25 90 180
N2XCY    2x2,5 RM/2,5  0,6/1kV 4441120 80 15 300 0.36 25 90 180
N2XCY      2x4 RE/4    0,6/1kV 4441130 123 15 360 0.57 40 90 180
N2XCY     2x10 RE/10   0,6/1kV 4441150 312 19 610 1.43 100 110 220
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.