BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

3-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627


AT33_N2XCY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 5G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
2X core insulation made of cross-linked polyethylene (XLPE)
C concentric Cu-conductor, Cu-tape counter helix
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCY 3 x 6 RE/6 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

3-cores acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCY    3x1,5 RE/1,5  0,6/1kV 4441104 66 14 270 0.21 23 90 180
N2XCY    3x2,5 RE/2,5  0,6/1kV 4441210 104 15 320 0.36 38 90 180
N2XCY      3x4 RE/4    0,6/1kV 4441124 161 16 400 0.57 60 100 200
N2XCY      3x4 RM/4    0,6/1kV 4441004 161 17 420 0.57 60 100 200
N2XCY      3x6 RE/6    0,6/1kV 4441240 240 17 500 0.86 90 100 200
N2XCY      3x6 RM/6    0,6/1kV 4441014 240 18 520 0.86 90 110 220
N2XCY     3x10 RE/10   0,6/1kV 4441114 408 19 700 1.43 150 120 240
N2XCY     3x16 RE/16   0,6/1kV 4441134 648 22 970 2.29 240 130 260
N2XCY     3x25 RM/16   0,6/1kV 4441144 902 26 1365 3.58 375 160 320
N2XCY     3x35 SM/16   0,6/1kV 4441154 1180 27 1590 5.01 525 160 320
N2XCY     3x50 SM/25   0,6/1kV 4441164 1713 30 2090 7.15 750 180 360
N2XCY     3x70 SM/35   0,6/1kV 4441174 2400 34 2840 10.01 1050 210 420
N2XCY     3x95 SM/50   0,6/1kV 4441184 3286 38 3810 13.59 1425 230 460
N2XCY    3x120 SM/70   0,6/1kV 4441194 4236 42 4760 17.16 1800 250 500
N2XCY    3x150 SM/70   0,6/1kV 4441604 5100 47 5730 21.45 2250 280 560
N2XCY    3x185 SM/95   0,6/1kV 4441614 6350 52 7150 26.46 2775 320 640
N2XCY    3x240 SM/120  0,6/1kV 4441624 8242 57 9180 34.32 3600 350 700
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.