BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

multicore acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627


AT336_N2XCY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-627 part 4H / HD 627 S1 and IEC 60502-1,
black cores with continuous numbering.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU), RoHS 2.0 and regulation No 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+90

Max. admissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

The core insulation of XLPE allows a higher operating temperature than comparable cable with PVC core insulation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
2X core insulation made of cross-linked polyethylene (XLPE)
C concentric Cu-conductor, Cu-tape counter helix
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCY 12 x 2,5 RE/4 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, concentric conductor, PVC, resp. PE sheath

N2XCY

multicore acc. to DIN VDE 0276-603, resp. DIN VDE 0276-627

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCY    7x1,5 RE/2,5  0,6/1kV 4446810 133 16 375 0.21 53 100 190
N2XCY    7x2,5 RE/2,5  0,6/1kV 4446800 200 17 465 0.36 88 110 210
N2XCY      7x4 RE/4    0,6/1kV 4446900 315 19 615 0.57 140 120 230
N2XCY   10x1,5 RE/2,5  0,6/1kV 4446820 176 19 495 0.21 75 120 230
N2XCY   10x2,5 RE/4    0,6/1kV 4424030 286 20 630 0.36 125 130 250
N2XCY     10x4 RE/6    0,6/1kV 4446910 443 23 855 0.57 200 140 270
N2XCY   12x1,5 RE/2,5  0,6/1kV 4446830 205 19 535 0.21 90 120 240
N2XCY   12x2,5 RE/4    0,6/1kV 4424040 334 21 690 0.36 150 130 260
N2XCY     12x4 RE/6    0,6/1kV 4446920 528 23 945 0.57 240 140 280
N2XCY   14x1,5 RE/2,5  0,6/1kV 4446840 234 20 580 0.21 105 120 240
N2XCY   14x2,5 RE/6    0,6/1kV 4446400 403 22 775 0.36 175 140 270
N2XCY     14x4 RE/6    0,6/1kV 4446930 619 21 1045 0.57 280 150 290
N2XCY   16x2,5 RE/6    0,6/1kV 4446410 451 23 860 0.36 175 140 280
N2XCY   19x1,5 RE/4    0,6/1kV 4446850 320 22 710 0.21 143 140 280
N2XCY   19x2,5 RE/6    0,6/1kV 4447400 523 24 950 0.36 238 150 290
N2XCY     19x4 RE/10   0,6/1kV 4446940 826 26 1325 0.57 380 160 320
N2XCY   24x1,5 RE/6    0,6/1kV 4446860 413 25 890 0.21 180 150 300
N2XCY   24x2,5 RE/10   0,6/1kV 4447410 696 27 1190 0.36 300 170 330
N2XCY   30x1,5 RE/6    0,6/1kV 4446870 499 26 1020 0.21 225 160 320
N2XCY   30x2,5 RE/10   0,6/1kV 4448200 840 28 1325 0.36 375 170 340
N2XCY   37x1,5 RE/6    0,6/1kV 4446890 612 28 1170 0.21 227 170 340
N2XCY   40x1,5 RE/10   0,6/1kV 4446880 696 29 1285 0.21 300 170 340
N2XCY   40x2,5 RE/10   0,6/1kV 4448210 1080 31 1660 0.36 500 190 380
N2XCY   52x2,5 RE/10   0,6/1kV 4448240 1342 36 2150 0.36 650 220 430
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.