Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XH-J

4-5-cores acc. to DIN VDE 0276


AT414_N2XH-J_4x_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse23-Halogenfrei24-Flammwidrig26-Raucharm50-Verlegung -5

optional

UV-beständig optional

Standards

DIN VDE 0276-604 and IEC 60502-1,
low gas corrosivity acc. to EN 50267,
low toxicity of gases acc. to DIN EN 50305,
low smoke density acc. to DIN EN 61034-2,
flame retardant acc. to IEC 60332-3, EN 50266-2-4.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

The cables are halogen-free, fire retardant and low-smoke.
(FRNC - flame retardant, non corrosive, LSOH - low smoke, zero halogen).

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
+90
Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994
during regular operation: B1
in case of short-circuit: B2
short-circuit duration max 5s
 

Application

Cable with improved behaviour in the event of fire.

For indoor and outdoor installation, in open air (protected against direct sun light), however not directly in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
H sheath made of thermoplastic, halogen-free polyolefin
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XH-J 4x50 SM 0,6/1 kV


Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XH-J

4-5-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XH-J     4x1,5 RE   0,6/1 kV 4411414 58 12 210 0.21 30 70 140
N2XH-J     4x2,5 RE   0,6/1 kV 4411424 96 13 260 0.36 50 80 160
N2XH-J       4x4 RE   0,6/1 kV 4411434 154 14 340 0.57 80 90 180
N2XH-J       4x6 RE   0,6/1 kV 4411444 230 15 440 0.86 120 90 180
N2XH-J      4x10 RE   0,6/1 kV 4411204 384 17 640 1.43 200 110 220
N2XH-J      4x16 RE   0,6/1 kV 4411454 614 19 900 2.29 320 120 240
N2XH-J      4x16 RM   0,6/1 kV 4411464 614 20 920 2.29 320 120 240
N2XH-J      4x25 RM   0,6/1 kV 4411474 960 24 1390 3.58 500 150 300
N2XH-J      4x35 SM   0,6/1 kV 4411484 1344 26 1710 5.01 700 160 320
N2XH-J      4x50 SM   0,6/1 kV 4432304 1920 29 2240 7.15 1000 180 360
N2XH-J      4x70 SM   0,6/1 kV 4410214 2688 33 3060 10.01 1400 200 400
N2XH-J      4x95 SM   0,6/1 kV 4410224 3648 37 4150 13.59 1900 230 460
N2XH-J     4x120 SM   0,6/1 kV 4410234 4608 41 5110 17.16 2400 250 500
N2XH-J     4x150 SM   0,6/1 kV 4410244 5760 46 6230 21.45 3000 280 560
N2XH-J     4x185 SM   0,6/1 kV 4410254 7104 51 7800 26.46 3700 310 620
N2XH-J     4x240 SM   0,6/1 kV 4410264 9216 57 10030 34.32 4800 340 680
N2XH-J     5x1,5 RE   0,6/1 kV 4437004 72 13 240 0.21 38 80 160
N2XH-J     5x2,5 RE   0,6/1 kV 4437014 120 14 310 0.36 63 80 160
N2XH-J     5x2,5 RM   0,6/1 kV 4437224 126 15 340 0.36 63 90 180
N2XH-J       5x4 RE   0,6/1 kV 4437024 192 15 400 0.57 100 90 180
N2XH-J       5x6 RE   0,6/1 kV 4437034 288 16 520 0.86 150 100 200
N2XH-J      5x10 RE   0,6/1 kV 4437044 480 19 760 1.43 250 110 220
N2XH-J      5x10 RM   0,6/1 kV 4436904 480 20 790 1.43 250 120 240
N2XH-J      5x16 RE   0,6/1 kV 4437054 768 21 1090 2.29 400 130 260
N2XH-J      5x16 RM   0,6/1 kV 4437064 768 22 1110 2.29 400 130 260
N2XH-J      5x25 RM   0,6/1 kV 4437074 1200 27 1700 3.58 625 160 320
N2XH-J      5x35 RM   0,6/1 kV 4437084 1680 30 2250 5.01 875 180 360
N2XH-J      5x50 RM   0,6/1 kV 4437094 2400 34 2960 7.15 1250 210 420
N2XH-J      5x70 RM   0,6/1 kV 4428604 3360 39 4150 10.01 1750 240 480
N2XH-J      5x95 RM   0,6/1 kV 4428614 4560 44 5550 13.59 2375 270 540
N2XH-J     5x120 RM   0,6/1 kV 4428624 5760 49 6950 17.16 3000 300 600
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.