BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XCH

1-2-cores acc. to DIN VDE 0276


AT421_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse23-Halogenfrei24-Flammwidrig26-Raucharm50-Verlegung -5

 


Standards

DIN VDE 0276-604 and IEC 60502-1,
low gas corrosivity acc. to EN 50267,
low toxicity of gases acc. to DIN EN 50305,
low smoke density acc. to DIN EN 61034-2,
flame retardant acc. to IEC 60332-3, EN 50266-2-4.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

The cables are halogen-free, fire retardant and low-smoke.
(FRNC - flame retardant, non corrosive, LSOH - low smoke, zero halogen).

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
  +90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994
during regular operation: B1
in case of short-circuit: B2
short-circuit duration max 5s
 

Application

Cable with improved behaviour in the event of fire.

For indoor and outdoor installation, in open air (protected against direct sun light), however not directly in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
C concentric Cu-conductor, Cu-tape counter helix
H sheath made of thermoplastic, halogen-free polyolefin
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCH 2x25 RM/16 0,6/1 kV


Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XCH

1-2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCH      1x6 RE/6    0,6/1kV 4423900 124 10 180 0.86 30 70 140
N2XCH     1x10 RE/10   0,6/1kV 4423910 202 11 260 1.43 50 80 160
N2XCH     1x16 RE/16   0,6/1kV 4423920 320 12 380 2.29 80 90 180
N2XCH     1x16 RM/16   0,6/1kV 4423930 320 12 380 2.29 80 90 180
N2XCH     1x25 RM/16   0,6/1kV 4423940 411 14 480 3.58 125 100 200
N2XCH     1x35 RM/16   0,6/1kV 4423950 518 15 580 5.01 175 110 220
N2XCH     1x50 RM/25   0,6/1kV 4423960 723 16 780 7.15 250 120 240
N2XCH     1x70 RM/35   0,6/1kV 4423970 1034 19 1090 10.01 350 140 280
N2XCH     1x95 RM/50   0,6/1kV 4423980 1428 21 1450 13.59 475 160 320
N2XCH    1x120 RM/70   0,6/1kV 4423990 1869 23 1880 17.16 600 180 360
N2XCH    1x150 RM/70   0,6/1kV 4424000 2147 25 2150 21.45 750 190 380
N2XCH    1x185 RM/95   0,6/1kV 4424010 2770 28 2770 26.46 925 210 420
N2XCH    1x240 RM/120  0,6/1kV 4424060 3495 31 3520 34.32 1200 240 480
N2XCH    1x300 RM/150  0,6/1kV 4424070 4511 34 4350 42.90 1500 260 520
N2XCH    2x1,5 RE/1,5  0,6/1kV 4470014 52 12 210 0.21 15 80 160
N2XCH    2x2,5 RE/2,5  0,6/1kV 4470004 80 13 250 0.36 25 80 160
N2XCH      2x4 RE/4    0,6/1kV 4470024 123 14 310 0.57 40 90 180
N2XCH      2x6 RE/6    0,6/1kV 4470034 182 15 390 0.86 60 90 180
N2XCH     2x10 RE/10   0,6/1kV 4470044 312 17 550 1.43 100 110 220
N2XCH     2x16 RE/16   0,6/1kV 4470054 489 20 780 2.29 160 120 240
N2XCH     2x25 RM/16   0,6/1kV 4481004 655 23 1090 3.58 250 140 280
N2XCH     2x35 RM/16   0,6/1kV 4471100 864 26 1360 5.01 350 160 320
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.