Download IconPrint Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XCH

multicore acc. to DIN VDE 0276


AT426_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse23-Halogenfrei24-Flammwidrig26-Raucharm50-Verlegung -5

optional

UV-beständig optional

Standards

DIN VDE 0276-627, part 7H and IEC 60502-1,
cores with black numbering printed,
low gas corrosivity acc. to EN 50267,
low toxicity of gases acc. to DIN EN 50305,
low smoke density acc. to DIN EN 61034-2,
flame retardant acc. to IEC 60332-3, EN 50266-2-4.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

The cables are halogen-free, fire retardant and low-smoke.
(FRNC - flame retardant, non corrosive, LSOH - low smoke, zero halogen).

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-5
  +90
Max permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

Cable with improved behaviour in the event of fire.

For indoor and outdoor installation, in open air (protected against direct sun light), however not directly in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
2X core insulation made of cross-linked polyethylene (XLPE)
C concentric conductor made of copper
H sheath made of thermoplastic, halogen-free polyolefin
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XCH 14x4 RE/6 0,6/1 kV


Print Icon

BayEnergy® flame retardant, non corrosive cables, FRNC/LSOH

N2XCH

multicore acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
N2XCH    7x1,5 RE/2,5  0,6/1kV 4470910 133 15 340 0.21 53 90 180
N2XCH    7x2,5 RE/2,5  0,6/1kV 4470800 200 16 420 0.36 88 100 200
N2XCH      7x4 RE/4    0,6/1kV 4470700 315 18 570 0.57 140 110 220
N2XCH   10x1,5 RE/2,5  0,6/1kV 4470920 176 18 450 0.21 75 110 220
N2XCH   10x2,5 RE/4    0,6/1kV 4470810 286 20 590 0.36 125 120 240
N2XCH     10x4 RE/6    0,6/1kV 4470710 443 22 780 0.57 200 130 260
N2XCH   12x2,5 RE/4    0,6/1kV 4470820 334 20 640 0.36 150 120 240
N2XCH     12x4 RE/6    0,6/1kV 4446950 528 22 880 0.57 240 140 280
N2XCH   14x1,5 RE/2,5  0,6/1kV 4470940 234 19 540 0.21 105 120 240
N2XCH   14x2,5 RE/6    0,6/1kV 4470830 403 21 730 0.36 175 130 260
N2XCH     14x4 RE/6    0,6/1kV 4470730 619 23 970 0.57 280 140 280
N2XCH   19x1,5 RE/4    0,6/1kV 4470950 320 21 670 0.21 143 130 260
N2XCH   19x2,5 RE/6    0,6/1kV 4470840 523 23 900 0.36 238 140 280
N2XCH     19x4 RE/10   0,6/1kV 4470740 826 26 1250 0.57 380 160 320
N2XCH   24x1,5 RE/6    0,6/1kV 4470960 413 24 840 0.21 180 150 300
N2XCH   24x2,5 RE/10   0,6/1kV 4470850 696 27 1140 0.36 300 160 320
N2XCH   30x1,5 RE/6    0,6/1kV 4470970 499 25 960 0.21 225 150 300
N2XCH   30x2,5 RE/10   0,6/1kV 4470860 840 28 1330 0.36 375 170 340
N2XCH   40x1,5 RE/10   0,6/1kV 4470980 696 29 1240 0.21 300 170 340
N2XCH   40x2,5 RE/10   0,6/1kV 4470870 1080 31 1650 0.36 500 190 380
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.