Download IconPrint Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

2XSCY

1-multicore based on IEC 60502-1


AT471_2XSCY_en
RoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!40-Geschirmt50-Verlegung -5

 


Standards

Based on IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

Technical Data

Rated voltage kV 0,6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +90
Short-circuit temperature °C +250

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks.

Type Designation Codes

2X core insulation made of cross-linked polyethylene (XLPE)
SC Screen made of copper foil and copper braid
Y outer sheath made of polyvinyl chloride (PVC)
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

2XSCY 7x2,5 RE/6 0,6/1 kV


Print Icon

BayEnergy® Power cables, XLPE insulation, screen, PVC sheath

2XSCY

1-multicore based on IEC 60502-1

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
2XSCY    2x2,5 RE/4    0,6/1kV 4445902 97 13 275 0.36 25 90 170
2XSCY      2x6 RE/8    0,6/1kV 4445910 212 15 435 0.86 60 100 200
2XSCY    4x2,5 RE/4    0,6/1kV 4445904 142 14 355 0.36 50 90 180
2XSCY      4x4 RE/8    0,6/1kV 4445912 246 16 485 0.57 80 110 210
2XSCY      4x6 RE/8    0,6/1kV 4445911 335 17 580 0.86 120 110 220
2XSCY      4x16RE/10   0,6/1kV 4445917 788 22 1090 2.29 320 140 280
2XSCY    7x2,5 RE/6    0,6/1kV 4445916 239 15 390 0.36 87 100 200
2XSCY   19x2,5 RE/8    0,6/1kV 4445920 601 22 835 0.36 237 140 270
2XSCY   27x2,5 RE/10   0,6/1kV 4445924 814 26 1105 0.36 337 170 330
2XSCY   37x2,5 RE/10   0,6/1kV 4445913 1069 29 1400 0.36 462 180 350
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.