Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

3-cores acc. to DIN VDE 0276


AT10_11_NYY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYY-J 3x120 SM 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

3-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYY-J       3x1,5 RE   0,6/1kV 4022104 43 13 240 0.00 0 0 0
NYY-J       3x2,5 RE   0,6/1kV 4022204 72 13 285 0.29 38 80 160
NYY-J         3x4 RE   0,6/1kV 4022304 115 15 390 0.46 60 100 200
NYY-J         3x6 RE   0,6/1kV 4022404 173 16 475 0.69 90 100 200
NYY-J        3x10 RE   0,6/1kV 4022504 288 18 640 1.15 150 110 220
NYY-J        3x16 RE   0,6/1kV 4022604 461 20 865 1.84 240 120 240
NYY-J        3x25 RM   0,6/1kV 4022704 720 24 1305 0.00 0 0 0
NYY-J        3x35 SM   0,6/1kV 4022804 1008 25 1525 4.03 525 160 320
NYY-J        3x50 SM   0,6/1kV 4023004 1440 28 1985 5.75 750 170 340
NYY-J        3x70 SM   0,6/1kV 4023104 2016 32 2655 0.00 0 0 0
NYY-J        3x95 SM   0,6/1kV 4023204 2736 36 3580 10.93 1425 220 440
NYY-J       3x120 SM   0,6/1kV 4023404 3456 39 4305 13.80 1800 240 470
NYY-J       3x150 SM   0,6/1kV 4023504 4320 44 5305 17.25 2250 260 520
NYY-J       3x185 SM   0,6/1kV 4023604 5328 49 6550 21.28 2775 300 600
NYY-J       3x240 SM   0,6/1kV 4023804 6912 54 8515 27.60 3600 330 660
NYY-J       3x300 SM   0,6/1kV 4023904 8819 60 10485 34.50 4500 360 720
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.