Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

1-2-cores acc. to DIN VDE 0276


AT10_11_NYY_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYY-J 1x120 RM 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, PVC sheath

NYY-J

1-2-cores acc. to DIN VDE 0276

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYY-J         1x6 RE   0,6/1kV 4019000 58 9 150 0.69 30 70 140
NYY-J        1x10 RE   0,6/1kV 4020200 96 10 200 1.15 50 80 150
NYY-J        1x16 RE   0,6/1kV 4020300 154 11 260 1.84 80 80 160
NYY-J        1x16 RM   0,6/1kV 4019800 154 11 270 1.84 80 90 170
NYY-J        1x25 RM   0,6/1kV 4019900 240 13 375 2.88 125 100 200
NYY-J        1x35 RM   0,6/1kV 4020500 336 14 475 4.03 175 110 210
NYY-J        1x50 RM   0,6/1kV 4020600 480 15 615 5.75 250 120 230
NYY-J        1x70 RM   0,6/1kV 4020700 672 17 825 8.05 350 130 260
NYY-J        1x95 RM   0,6/1kV 4020800 912 19 1105 10.93 475 150 300
NYY-J       1x120 RM   0,6/1kV 4020900 1152 21 1350 13.80 600 160 310
NYY-J       1x150 RM   0,6/1kV 4021000 1440 22 1660 17.25 750 170 340
NYY-J       1x185 RM   0,6/1kV 4021100 1776 25 2015 21.28 925 190 370
NYY-J       1x240 RM   0,6/1kV 4019700 2304 27 2595 27.60 1200 210 420
NYY-J       1x300 RM   0,6/1kV 4021300 2880 30 3210 34.50 1500 230 460
NYY-J       1x400 RM   0,6/1kV 4019600 3840 33 4125 41.20 2000 260 520
NYY-J       1x500 RM   0,6/1kV 4020000 4800 37 5205 51.50 2500 280 560
NYY-J       1x630 RM   0,6/1kV 4019500 6048 41 6450 64.89 3150 320 640
(N)YY-J     2x1,5 RE   0,6/1kV 4021400 29 12 215 0.17 15 80 160
(N)YY-J     2x2,5 RE   0,6/1kV 4021500 48 13 250 0.29 25 85 170
(N)YY-J       2x4 RE   0,6/1kV 4021600 77 15 340 0.46 40 90 180
(N)YY-J       2x6 RE   0,6/1kV 4021700 115 16 410 0.69 60 100 200
(N)YY-J      2x10 RE   0,6/1kV 4021800 192 17 535 1.15 100 110 220
(N)YY-J      2x16 RE   0,6/1kV 4022000 307 19 705 1.84 160 120 240
(N)YY-J      2x25 RM   0,6/1kV 4098700 480 24 1105 2.88 250 150 300
(N)YY-J      2x35 RM   0,6/1kV 4002500 672 25 1330 4.03 350 160 320
(N)YY-J      2x50 RM   0,6/1kV 4002600 960 29 1745 5.75 500 175 350
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.