Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-O

3-, 4-, 5-cores and multicore acc. to DIN VDE 0265


AT16_NYKY-O_en
VDE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optional

Standards

DIN VDE 0265 and IEC 60502-1,
from 7 cores with black numbering printed.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160

Current carrying capacity

3 and 4 cores:
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s

multi-core
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, especially in applications where there is the influence of solvents, fuels, oils, gasoline or similar must be expected (e.g., refineries and gas stations).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
K lead sheath
Y outer sheath made of polyvinyl chloride (PVC)
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYKY-O 4x35 SM 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-O

3-, 4-, 5-cores and multicore acc. to DIN VDE 0265

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NYKY-O     1x300 RM   0,6/1 kV 4335270 2880 1710 32 4660 34.50 0 0 0
NYKY-O     3x35 SM/16 RE       0,6/1 kV 4336204 1162 1340 31 3295 4.03 525 190 380
NYKY-O       4x6 RE   0,6/1 kV 4335404 230 665 19 1165 0.69 120 115 230
NYKY-O      4x35 SM   0,6/1 kV 4337504 1344 1340 29 3195 4.03 700 180 360
NYKY-O     5x1,5 RE   0,6/1 kV 4331604 72 505 15 765 0.17 38 100 200
NYKY-O     7x1,5 RE   0,6/1 kV 4330900 101 545 16 850 0.17 53 105 210
NYKY-O     7x2,5 RE   0,6/1 kV 4332600 168 625 17 980 0.29 88 110 220
NYKY-O    16x2,5 RE   0,6/1 kV 4333400 384 1470 24 1765 0.29 200 145 290
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.